X5 AC Drive User’s Manual
Chapter 7: X5 Parameters
DPD00089A
-
98 -
© 2009 Vacon Incorporated All Rights Reserved
750 Timer 2 Signal
Default: DI-R/J
Range: n/a
Level 2
This parameter selects the function that the timer is counting; it includes any function listed in the digital input list.
See Parameter
, Relay 1 Select, on page 93 for the list of options. For detailed information about setting up Timer
parameters, see
751 Timer 2 Time
Default: 1.0 sec
Range: 0.0-320.0 sec
Level 2
This parameter specifies the duration of time in seconds for the timer to count. For detailed information about setting up
Timer parameters, see
.
794 Drive Name
Default: Drive serial number
Range: n/a
Level 2
799
) will have a filename associated with parameter
794
(Drive Name). The complete drive serial
number is composed of the data found in parameters
005
and
006
, and is also found on the drive nameplate.
799 Config USB Mode
Default: Disabled
Range: n/a
Level 2
This parameter allows you to select what kind of data you want to store in a flash memory device such as a thumb drive
or memory stick. For more information on using a flash memory device with the X5, see
Option
Description
0
Disabled
1
Parameter Store to USB
2
Parameter Recall from USB
3
Keeper Dump
Table 7-2: Description of X5 Parameters