FORM DPD01347
7/2013
WARNING -IMPORTANT INSTRUCTIONS for your
VACON® X5 HazLo© AC Drive
VACON® X5 HazLo© AC Drives are readily recognizable by the safety yellow covers and one (1) of the
following type codes:
VACONX5C40400X
VACONX5C40500X
VACONX5C40600X
VACONX5C40750X
VACONX5C41000X
If using option board, the only permitted option boards are:
X5OPT01X
115 Vac and Encoder Feedback Option Card
X5EIP01X
Ethernet IP Option Card
X5DNET01X DeviceNet Option Card
X5MBTCP01X ModBus TCP/IP Option Card
X5PROFI01X ProfiBus Option Card
Location:
The hazardous location certification is for Class 1 Division 2 Group A, B, C, D for further information see
http://www.osha.gov/doc/outreachtraining/htmlfiles/hazloc.html
.
Warning Explosion Hazard:
Substitution of any components may impair suitability for Class 1 Division 2. DO NOT disconnect
equipment while circuit is live or unless the area is known to be free of ignitable concentrations.
Warning:
Exposure to some chemicals may degrade the sealing properties of materials used in the relays inside of
the drive.
Product Data:
Product
Voltage
HP
Il A
Dimension
Frame
VACONX5C40400X
480
40
52
11,19x20,19x11,73
T3
VACONX5C40500X
480
50
65
11,19x20,19x11,73
T3
VACONX5C40600X
480
60
77
12,84x29,35x13,8
T4
VACONX5C40750X
480
75
96
12,84x29,35x13,8
T4
VACONX5C41000X
480
100
124
12,84x29,35x13,8
T4
Installation Requirements:
Use only 75C copper wire. Suitable for use on a circuit capable of delivering not more than 65,000 rms
symmetrical amperes, 480 Volts maximum, when protected by Class T fuses. These devices provide
overload protection at 120% of full load amperes. Integral solid state short circuit protection does not
provide branch circuit protection. Branch circuit protection must be in accordance with the National
Electrical Code and any additional local codes.
Installation Manual:
For further installation directions and dimensions see manual DPD00089.