X5 AC Drive User’s Manual
Chapter 7: X5 Parameters
DPD00089A
-
76 -
© 2009 Vacon Incorporated All Rights Reserved
Parameter
202,
the
Rev Enable
parameter, configures whether the REV key on the keypad is functional. If this
parameter is configured to “Forward,” then pressing the REV key on the keypad will have no effect. Note that this
parameter does not affect terminal strip operation.
The following data values may be assigned to this parameter:
Parameter Value
Description
Forward
Forward Only, REV key disabled
FWD/REV
FWD and REV keys enabled
203 Stop Key Remote
Default = Coast
Range: n/a
Level: 2
Parameter
203,
the
Stop Key Remote
parameter, configures how the Stop key on the keypad will operate when the
keypad is not the drive’s control source (terminals, SIO, or SEQ).
The following data values may be assigned to this parameter:
Parameter Value
Description
Coast
Drive will coast to a stop
Ramp
Drive will ramp to a stop using Decel #1
Disabled
Stop key will have no function
204 Ref Select
Default = Vin1
Range: n/a
Level: 2
Parameter
204
, the
Ref Select
parameter, configures how the reference is determined when the reference source is
configured to terminals.
The following data values may be assigned to this parameter:
Parameter Value
Description
parameter 205
)
Cin
parameter 208
)
Vin2
parameter 211
)
Vin1 6FS
Vin1 terminal with 6x pulse train from an X5, WFC, WF2 drive
Vin1 48FS
Vin1 terminal with 48x pulse train from an X5, WFC, WF2 drive
Vin1+Cin
Sum of signal at Vin1 and the signal at Cin
Vin1+Vin2
Sum of signal at Vin1 and the signal at Vin2
Vin1-Cin
Difference between the signal at Vin and the signal at Cin
Vin1-Vin2
Difference between the signal at Vin and the signal at Vin2
Max Input
{2}
Greatest signal between Vin, Vin2 and Cin
Vin1/Cin DI
{1}
Switch between Vin and Cin using a Digital Input
Vin1/2 DI
{1}
Switch between Vin and Vin2 using a Digital Input
Vin1/KYP DI
{1}
Switch between Vin and Keypad reference using Digital Input
Cin/KYP DI
{1}
Switch between Cin and Keypad reference using Digital Input
Notes:
1. The parameter that sets the function of the designated digital input must be configured as “Ref Switch” to complete the implementation.
2. The “Max Input” option will compare the inputs of all three analog inputs (Vin1, Vin2, Cin) and take the analog input with the highest
percentage input after span, offset, and inversion is applied.
Table 7-2: Description of X5 Parameters
(Page 6 of 40)