SMGM-SC: EQUIPMENT CONFIGURATION IN THE TIA PORTAL
121
12
SMGM-SC: EQUIPMENT CONFIGURATION IN
THE TIA PORTAL
12.1 General
The SMGM-SC module must be integrated in the PLC device configuration through the provided GSDML equip-
ment description file. For this purpose, the GSDML file must be installed in the HW catalog, as is customary in
the SIEMENS TIA Portal. Afterwards, the installed components can be integrated into the HW configuration.
An example configuration is depicted in the following representation.
Fig. 12-1 Configuration example
Each integrated system controller (SMGM-SC) requires an address range of 198 input and 8 output bytes.