Appendix
24
Installation and maintenance instructions recoVAIR 0020188110_03
F
Maintenance messages
–
Overview
#
Message
Description
Maintenance work
Interval
1
M.800 Filter
change
The maintenance interval for
the filters was exceeded.
Maintaining the filters
At least twice annually
17
2
M.801 Mainten-
ance
The maintenance interval for
the product was exceeded.
Maintaining the product
At least annually
3
M.802 System ef-
ficiency impaired
The system efficiency is ad-
versely affected.
Increase/establish system effi-
ciency
As required
17
G
Technical data
VAR 150/4 L
VAR 150/4 R
Width
1,412 mm
1,412 mm
Depth
598 mm
598 mm
Height
249 mm
249 mm
Product with packaging
42 kg
42 kg
Product without packaging/ready for
operation
35.8 kg
35.8 kg
Rated voltage/measuring voltage of
the control circuit
230 V
230 V
Power frequency
50 Hz
50 Hz
Fuse, slow-blow
4 A
4 A
Power consumption
4 … 84 W
4 … 84 W
Max. power consumption (with frost
protection element, if available)
684 W
684 W
Current consumption
0.37 A
0.37 A
Minimum cross-section of the supply
line
≥
1.5 mm
²
≥
1.5 mm
²
Protection class
1
1
Level of protection
IP10B
IP10B
Air connection area diameter (internal)
150 mm
150 mm
Air connection area diameter (external)
180 mm
180 mm
Heat exchanger material
PET C/aluminium
PET C/aluminium
Max. air volume flow
150 m
³
/h
150 m
³
/h
Nominal flow
70 … 115 m
³
/h
70 … 115 m
³
/h
Remaining delivery pressure at max.
air volume flow
130 Pa
130 Pa
Specific power consumption at max.
nominal flow and external compres-
sion
0.4 W/(m
3
/h) at
115 m
3
/h, 100 Pa
0.4 W/(m
3
/h) at
115 m
3
/h, 100 Pa
Specific power consumption in ac-
cordance with the Passivhaus Institut
(Passive House Institute)
0.4 W/(m
3
/h) at
115 m
3
/h, 100 Pa
0.4 W/(m
3
/h) at
115 m
3
/h, 100 Pa
Ourdoor air filter class (in accordance
with EN 779)
F7/F9
F7/F9
Ourdoor air filter class (in accordance
with ISO 16890)
ISO ePM2,5
70%/ISO ePM1,0
85%
ISO ePM2,5
70%/ISO ePM1,0
85%
Extract air filter class (in accordance
with EN 779)
G4
G4
Extract air filter class (in accordance
with ISO 16890)
ISO Coarse
ISO Coarse
Filter surface
0.5 m
²
0.5 m
²
Thermal efficiency in accordance with
EN 13141-7
82 %
82 %