background image

6

Operating manual atmoCRAFT

mode is achieved when all rooms in an apartment are 
heated uniformly and in accordance to their usage.
The building structure can also suffer if components of 
the building are unheated or only inadequately heated.

Thermostat valves and room thermostat

It should be a matter of course, today, that all radiators be 
fitted with thermostatic valves. They exactly maintain the 
set room temperature. You can adjust the room 
temperature to suit your individual requirements and 
ensure effective operation of your heating installation 
using the thermostatic valves in combination with a room 
temperature regulator (weather compensator).
In the room where the room temperature regulator is 
located, all the radiator valves should be fully opened since 
otherwise the two regulating systems will work against 
each other and the regulation quality can be affected.
The following actions by the user are seen quite often: 
As soon as the temperature in the room gets too hot, 
the thermostatic valves are turned down (or the room 
thermostat is set to a reduced temperature). If it gets 
too cold again after a time, the thermostatic valve is 
opened up again.
This is not necessary since the temperature regulation 
system takes over this task via the thermostatic valve: If 
the room temperature rises above the value set on the 
sensor head, the thermostat valve shuts off 
automatically, and when the temperature drops below 
the defined value, it opens again.

Do not cover regulators

Do not cover your regulators with furniture, drapes or 
similar objects. The room air must circulate unhindered. 
Covered thermostat valves can be equipped with remote 
sensors and thus still work.

Appropriate hot water temperature

The warm water should only be heated up to the extent 
that is necessary for use. Any further heating results in 
unnecessary power consumption and hot water 
temperatures of more than 60 °C also lead to increased 
lime scale production.

Energy-conscious use of water

Energy-conscious use of water can reduce your bills 
considerably.
For example, taking a shower instead of a bath: whereas 
about 150 litres of water are required for a bath, a 
modern shower equipped with water saving fittings only 
requires a third of this water quantity. Incidentally: a 
dripping water tap wastes up to 2000 litres of water and 
a leaking toilet flush up to 4000 litres of water each year. 
On the other hand, a new seal only costs a few cents.

Run circulation pumps only if needed

Hot water piped systems are often fitted with so-called 
circulation pumps. These provide continuous re-
circulation of hot water in the piping system so that hot 
water is immediately available, even at drawing-off 
points which are located far away.
These circulation pumps can also be used with the 
Vaillant atmoCRAFT. There is no doubt that they provide 
increased comfort for hot water heating. Please bear in 
mind, however, that these pumps consume electricity. 
And circulating hot water that is not used cools off when 
passing through pipes and then needs to be reheated. 
Therefore, circulation pumps are to be operated only 
when hot water is actually needed for the household.
By using switch clocks, with which most circulation 
pumps are equipped, individual time programmes can be 
defined. Weather compensators often have ancillary 
functions for controlling circulation pump timings. 
Consult your heating engineer.

Ventilating residential spaces

During the heating period, open windows only for 
ventilation and not for temperature regulation. A brief 
impact-ventilation is more effective and energy-saving 
than windows that are kept open for a long time. We 
recommend that the windows be opened fully for a short 
period. During ventilation, close all thermostatic valves 
in the room or set the room regulator to minimum 
temperature. In this way, there will be adequate 
ventilation without unnecessary cooling and energy loss 
(e.g. by the heating switching on during the ventilation 
procedure).

3 Notes on the installation and operation

Summary of Contents for atmoCRAFT VK SERIES

Page 1: ...VK 654 9 1654 9 atmoCRAFT DE AT GB CZ SK HU PL HR SI SCG...

Page 2: ...For the owner VK 654 9 1654 9 Operating manual atmoCRAFT Gas heating boiler GB...

Page 3: ...by exceeding the temperature 13 4 8 5 Faults with the exhaust gas removal 13 4 8 6 Filling unit heating installation 14 4 9 Shut down 14 4 10 Frost protection 15 4 10 1 Frost protection function 15 4...

Page 4: ...4 Data badge The identification plate is included with the burner and should be mounted on the separation wall 2 Safety What to do in an emergency Danger If you smell gas risk of poisoning and explos...

Page 5: ...sufficiently heated Caution Risk of damage If there is a power cut or if the room temperature is set too low in individual rooms it cannot be ruled out that sections of the heating system are damaged...

Page 6: ...en by the heating engineer The desired heating and set back phases e g at night are automatically turned on and off using the integrated time programmes Weather compensators combined with thermostat v...

Page 7: ...0 C also lead to increased lime scale production Energy conscious use of water Energy conscious use of water can reduce your bills considerably For example taking a shower instead of a bath whereas ab...

Page 8: ...nk temperature in normal mode if a storage tank sensor is connected 6 button for moving backwards in the display for adjustment and troubleshooting by the engineer 7 Reset button for resetting certain...

Page 9: ...0 6 5 4 3 bar 1 Fig 4 4 Checking the filling pressure of the heating installation pressure gauge not included Check the filling pressure of the installation using the pressure gauge 1 not included For...

Page 10: ...ng feed temperature Note We recommend a setting of 60 C for economic and hygienic reasons e g Legionella Caution Danger of calcium deposit build up If your water hardness is more than 1 79 mol m3 10 d...

Page 11: ...m fitted to your heating system 4 5 2 Setting the flow temperature no controller connected 1 2 Fig 4 8 Feed temperature setting without heating controller If there is no external controller set the fl...

Page 12: ...tion of your boiler Press the i button 1 to activate the status displays The display 2 then shows the individual status codes e g S 4 for burner operation The table below explains the most important s...

Page 13: ...he heating system see Section 4 8 2 Is there an ignition problem see Section 4 8 3 Hot water operation no problem Heating does not start Is there a requirement for heating from the external controller...

Page 14: ...exceeding the temperature 1 2 Abb 4 14 Releasing after STB switch off Your boiler is equipped with a safety temperature limiter STB which automatically switches off the boiler if the temperature gets...

Page 15: ...However in exceptions the water quality might not be suitable for filling in the heating system heavily corrosive or extremely calciferous water In a case such as this you should please contact your a...

Page 16: ...he frost protection system cannot guarantee flow through the entire heating system 4 10 2 Frost protection by draining Another way to protect the heating system and the appliance from frost is to drai...

Page 17: ...ed as follows to perform the measurements Activate the chimney sweep mode by simultaneously pushing the buttons 6 and 7 on the DIA System The measurements should be taken at the earliest after 2 minut...

Reviews: