Technical Specifications
Units
VAM 2-050 W2N
VAM 2-060 W2N
VAM 2-085 W3N
VAM 2-110 W4N
Power supply
V/Ph/Hz
230/1/50
Cooling Capacity
kW
5,20
5,40
8,10
9,10
Power input
kW
1,62
1,66
2,48
2,78
Operating current
A
7,00
7,20
10,80
12,10
Heating Capacity
kW
6,10
6,25
9,05
10,10
Power input
kW
1,67
1,73
2,49
2,78
Operating current
A
7,30
7,50
10,80
12,10
Indoor Unit
Air Flow volume 1
m
3
/h
250/300/500
250/300/500
250/300/500
250/300/500
Air Flow volume 2
m
3
/h
250/300/500
310/450/580
250/300/500
250/300/500
Air Flow volume 3
m
3
/h
/
/
310/450/580
250/300/500
Air Flow volume 4
m
3
/h
/
/
/
310/450/580
Sound Pressure level 1
dB(A)
26/32/38
26/32/38
26/32/38
26/32/38
Sound Pressure level 2
dB(A)
26/32/38
28/35/40
26/32/38
26/32/38
Sound Pressure level 3
dB(A)
/
/
28/35/40
26/32/38
Sound Pressure level 4
dB(A)
/
/
/
28/35/40
Outdoor Unit
Air Flow volume
m
3
/h
2500
2500
2500
3500
Sound Pressure level
dB(A)
52
52
55
57
Refrigerant
R410A
Refrigerant charge
gr
1450
1450
2000
2400
Compressor type
Rotary
Expansion system
EXV + Capillary
Pipe Connections
Diameter liquid/gas pipes
Inches
1/4" - 3/8"
1/4" - 3/8"
1/4" - 3/8"
1/4" - 3/8"
Max. L1 + L2 + (L3) + (L4)
m
30
30
45
60
Max. L1
m
15
15
15
15
Max. height IU under OU
m
10
10
10
10
Max. height OU under IU
m
10
10
10
10
Chargeless length
m
7,5
7,5
7,5
7,5
Additional charge per metre
gr
15
15
15
15