Installation 5
0020230535_05 ecoFIT pure Installation and maintenance instructions
13
5.6.1.6 External termination into soakaway
400mm min
300mm
min
25mm min
500mm min
Ø100mm
L = 3m max
Ø19mm
min
Ø30mm
5.6.1.7 External termination into rain water down
pipe
Ø19mm
min
Ø30mm
5.7
Flue installation
5.7.1
Installing and connecting the flue pipe
1.
You can find out which flue pipes may be used by con-
sulting the enclosed flue pipe installation manual.
2.
Observe the information on positioning the opening
for the flue pipe. This information can be found in the
appendix.
Conditions
: Installation in damp rooms
▶
You must connect the product to a room-sealed air/flue
gas installation. The combustion air must not be taken
from the installation site.
Caution.
Risk of poisoning due to escaping flue
gas.
Mineral-oil-based greases can damage the
seals.
▶
Instead of grease, use only water or com-
mercially available soft soap to aid install-
ation.
3.
Install the flue pipe using the installation manual.
5.8
Electrical installation
Danger!
Risk of death from electric shock!
Continuous voltage is present at power sup-
ply terminals L and N even when the unit is
switched off using the standby button.
▶
Switch off the power supply.
▶
Secure the power supply against being
switched on again.
Only qualified electricians may carry out the electrical install-
ation.
5.8.1
Opening the electronics box
B
B
A
▶
Follow the instructions in the specified sequence.
5.8.2
Cable route
2
1
1
230-V cable route
2
24-V cable or eBUS
cable route