7 Start-up
16
Installation and maintenance instructions ecoFIT pure 0020230535_05
6.5
Using check programmes
Call up the installer level + 1 x
Display
Meaning
P.00
Purging check programme:
The internal pump is cyclically actuated.
The heating circuit and the hot water circuit are
purged via the automatic air vent (the cap of the
automatic air vent must be released).
1 x
: Start heating circuit purging
2 x
(
→
): Start domestic hot water circuit
purging
3 x
(
→
): Restart heating circuit purging
1 x
(
Cancel
): End purge programme
Note
The purge programme runs for 7.5 min per circuit
and then terminates.
Purging the heating circuit:
Prioritising diverter valve in heating position, ac-
tuation of internal pump for 9 cycles: 30 sec. on,
20 sec. off. Display:
Active heating circuit
.
Purging the hot water circuit:
After the above-mentioned cycles have run or the
right-hand selection button has been pressed again:
Prioritising diverter valve in the domestic hot water
position, actuation of the internal pump as above.
Display:
Active hot water circuit
.
P.01
Maximum load check programme:
After successful ignition, the product is operated at
maximum heat input.
P.02
Minimum load check programme:
After successful ignition, the product is operated at
minimum heat input.
P.06
Filling mode check programme:
The prioritising diverter valve is moved to the mid-
position. The burner and pump are switched off (to
fill or drain the product).
7
Start-up
7.1
Carrying out the initial start-up
Initial start-up must be carried out by a customer service
technician or an authorised competent person using the first-
commissioning-checklist. The first-commissioning-checklist
in the appendix (
→
Page 37) of the installation instructions
must be filled out and stored carefully along with the unit's
documentation.
▶
Carry out the initial start-up using the first-commission-
ing-checklist in the appendix.
▶
Fill out and sign the first-commissioning-checklist.
7.2
Checking the factory setting
The product's combustion has been factory tested and is
preset for operation with the gas group indicated on the iden-
tification plate.
The product is only authorised to be operated with natural
gas.
▶
Check the information about the type of gas indicated on
the identification plate and compare this with the type of
gas available at the installation location.
Conditions
: The product design
is not compatible
with the local gas
group
▶
Do not start up the product.
Conditions
: The product design
is compatible
with the local gas group
▶
Proceed as described below.
7.3
Checking and treating the heating
water/filling and supplementary water
Caution.
Risk of material damage due to poor-qual-
ity heating water
▶
Ensure that the heating water is of suffi-
cient quality.
▶
Before filling or topping up the installation, check the
quality of the heating water.
Checking the quality of the heating water
▶
Remove a little water from the heating circuit.
▶
Check the appearance of the heating water.
▶
If you ascertain that it contains sedimentary materials,
you must desludge the installation.
▶
Use a magnetic rod to check whether it contains mag-
netite (iron oxide).
▶
If you ascertain that it contains magnetite, clean the in-
stallation and apply suitable corrosion-protection meas-
ures, or fit a magnetic filter.
▶
Check the pH value of the removed water at 25 °C.
▶
If the value is below 6.5 or above 8.5, clean the system
and treat the heating water.
▶
Ensure that oxygen cannot get into the heating water.
Checking the filling and supplementary water
▶
Before filling the installation, measure the hardness of the
filling and supplementary water.
Treating the filling and supplementary water
▶
Observe all applicable national regulations and technical
standards when treating the filling and supplementary
water.
Provided the national regulations and technical standards
do not stipulate more stringent requirements, the following
applies:
You must treat the heating water in the following cases:
–
If the entire filling and supplementary water quantity dur-
ing the operating life of the system exceeds three times
the nominal volume of the heating installation, or
–
If the guideline values listed in the following table are not
met, or