Appendix
28
Installation and maintenance instructions ecoFIT pure 0020230535_05
Setting level
Values
Unit
Increment, select, explanation
Default set-
ting
Own setting
Min.
Max.
d.20 Maximum hot water set
target temperature
50
60
℃
1
50
Adjustable
d.23 Status of the heating de-
mand
Current value
–
off = Heating off (Summer mode)
on = Heating on
–
Not
adjustable
d.24 Status of the pressure
monitor
0
1
–
off = Not switched
on = Switched
–
Not
adjustable
d.25 Status of the requirement
to reheat the cylinder or for
the hot water warm start from
the eBUS thermostat
Current value
–
off = Function deactivated
on = Function activated
–
Not
adjustable
d.27 Function of relay 1 (multi-
functional module)
1
10
–
1 = Circulation pump
2 = External pump
3 = Cylinder charging pump
4 = Extractor hood
5 = External solenoid valve
6 = External fault message
7 = Solar pump (omitted)
8 = eBUS remote control
9 = Legionella protection pump
10 = Solar valve
1
Adjustable
d.28 Function of relay 2 (multi-
functional module)
1
10
–
1 = Circulation pump
2 = External pump
3 = Cylinder charging pump
4 = Extractor hood
5 = External solenoid valve
6 = External fault message
7 = Solar pump (omitted)
8 = eBUS remote control
9 = Legionella protection pump
10 = Solar valve
2
Adjustable
d.31 Automatic filling device
0
2
–
0 = Manual
1 = Semi-automatic
2 = Automatic
0
Adjustable
d.33 Fan speed target value
Current value
rpm
Fan speed = Display value x 100
–
Not
adjustable
d.34 Value for the fan speed
Current value
rpm
Fan speed = Display value x 100
–
Not
adjustable
d.40 Heating flow temperature
Current value
℃
–
–
Not
adjustable
d.41 Heating return temperat-
ure
Current value
℃
–
–
Not
adjustable
d.43 Heating curve
0.2
4
–
0.1
1.2
Adjustable
d.45 Value for the base point
of the heating curve
15
30
–
1
20
Adjustable
d.47 Outside temperature
Current value
℃
–
–
Not
adjustable
d.50 Correction of the min-
imum fan speed
0
3000
rpm
1
Fan speed = Display value x 10
600
Adjustable
d.51 Correction of the max-
imum fan speed
-2500
0
rpm
1
Fan speed = Display value x 10
-1000
Adjustable
d.58 Solar circuit reheating
0
3
–
0 = Boiler's Legionella protection
function deactivated
3 = Hot water activated (target value
min. 60 °C)
0
Adjustable
d.60 Number of blocks by the
temperature sensor
Current value
–
–
–
Not
adjustable
d.61 Number of successful
ignitions
Current value
–
–
–
Not
adjustable
d.62 Night set-back
0
30
–
1
0
Adjustable