Instructions for Use, Installation and Servicing ecoMAX pro
26
14 Servicing
Overview of the inspection and maintenance tasks
Activity
Column
1
Column 2
1
Check the air/ gas flue system and ensure it is not blocked, damaged and is fitted correctly.
x
2
Measure the gas rate during operation (see table 5.1. inside section 5 commissioning part I). If
the gas rate is lower than the minimum gas rate, follow the maintenance schedule in column 2.
x
3
Check combustion by measuring CO and CO2 values, compare to table 9.1. If the measure-
ment is outside the tolerances follow the maintenance schedule in column 2. If a flue gas ana-
lyser is not available check the ignition and burner flame picture through the viewing window if
incomplete combustion is evident perform the maintenance schedule in column 2.
x
4
Isolate the appliance from the electrical mains supply, close the gas service valve.
x
5
Visually inspect the general heat exchanger area for signs of corrosion, sooting or other forms
of damage. If damage is evident perform the tasks in the maintenance schedule in column 2.
x
6
Remove the burner module (as described in section 8.1.6.) if maintenance schedule is required
from steps 2, 3 or 5 above. Clean the primary heat exchanger. Fit new burner door seal kit
(observe the assembly instructions enclosed with the kit). Refit the burner module and tighten
the nuts.
x
7
Check all appliance electrical connections and make adjustments, if necessary.
x
x
8
If applicable check/re-pressurise system expansion vessel as necessary.
x
x
9
Check the appliance generally, check for dirt/dust and clean if necessary.
x
x
Check and clean condensate trap and flexible condensate hose.
x
x
Perform a test operation of the appliance including the heating and hot water systems and
bleed thew system if necessary.
x
x
Measure the gas rate during operation and ensure it is inside the tolerances specified (see
table 5.1 inside section 5 commissioning part I).
x
Re-check combustion by measuring CO and CO2 values, compare to table 9.1. Ensure the
measurement is within the tolerances. If a flue gas analyser is not available check the ignition
and burner flame picture visually. through the viewing window.
x
Check boiler for leaks of any kind, rectify as necessary.
x
x
Complete gas boiler commissioning checklist (Benchmark).
x
x
Summary of Contents for ecoMAX pro 18E
Page 37: ...Instructions for Use Installation and Servicing ecoMAX pro 37 Declaration of Conformity 17...
Page 38: ...Instructions for Use Installation and Servicing ecoMAX pro 38...
Page 39: ...Instructions for Use Installation and Servicing ecoMAX pro 39...
Page 40: ...0020005557_04 GB 08 2006 Subject to alteration...