Installing the flue gas pipe on the external wall
Installation manual for the flue pipe for ecoTEC plus 0020137851_02
25
8
1
2
3
5
4
6
8.13 Shortening the roof duct
Key
1 Roof
duct
2 Fastening
clamp
3 External pipe of the roof duct
4 Internal pipe of the roof duct
5 Connecting
sleeve
>
Pull the connecting sleeve (
6
) out of the external pipe
(
3
).
>
Shorten the external pipe (
3
) and the flue pipe by an
equal distance (maximum 20 cm).
>
Place the connecting sleeve (
6
) back into the external
pipe (
3
).
>
Drill a hole (
4
) with a diameter of 3 mm through the
external pipe and through the connecting sleeve (
6
).
>
Install the safety screw.
>
Connect all the flue components under the roof.
>
Connect up all the flue components above the roof
(extensions, opening piece, clamps).
>
Install all the pipe brackets.
>
Attach the fastening clamps of the roof duct to the raft-
ers or ceiling.
If opening heights of more than 1.5 m are required, the roof
duct must be anchored.
1
4
2
3
8.14
Anchoring above the roof
If the roof duct protrudes by more than 1.5 m above the tile
(
3
), the roof duct must be secured above the roof.
>
Attach clamps (
1
) to all the connecting points above the
tile.
>
Attach a pipe bracket (
2
) to the pipe above the roof.
>
Connect this pipe bracket to the roof construction using
struts (
4
) or rope.
8.3.5
Shortening an extension
2
1
8.15
Shortening an extension