5 Set-up
14
Set-up instructions 0020200969_07
The mounting template indicates the position for horizontal
installation of the air/flue pipe when connecting it to the up-
per side of the boiler.
Condition
: Top connection, air/flue pipe to the side
A
A =
125 mm
If you want to install the air/flue pipe laterally, you can de-
termine the position of the wall duct by carefully offsetting the
central line of the wall duct that is marked on the mounting
template.
▶
Calculate the required gradient in accordance with the
length of the flue pipework and then mark the position for
the wall duct.
5.2.2
Determining the clearance to the external
wall
A
C
A
B
C
1.
2.
1.
Upper flue pipe at the
rear
2.
Upper flue pipe to the
side
A
Clearance to the ex-
ternal wall
B
Clearance to the in-
ternal wall: 105 mm
▶
Measure the clearance
(A)
from outside of the wall to the
centre of the connector.
Clearance to the external wall (
Clearance
Article number
0010035512
0020219517
0020219519
C
87 mm
140 mm
5.2.3
Installing the 60/100 mm diameter horizontal
wall/roof duct, article number 0020219517 or
0010035512
5.2.3.1 Scope of delivery 0020219517
65
832
Ø167
65
30
40
1
2
3
4
5
1
Wall collar, 100 dia-
meter (2 pcs)
2
Horizontal wall duct
3
40 mm clamp
4
87° elbow
5
30 mm clamp