Technical data
112
Installation instructions geoTHERM 0020051574_04
14
Description
Unit
VWS 220/2
VWS 300/2
VWS 380/2
VWS 460/2
Heat pump performance data
The following performance data is applicable to new units with clean heat exchangers.
B0/W35
D
T 5K In accordance with
DIN EN 14511
- Heating output
- Power consumption
- Output figure/coefficient
of performance COP
B0/W35
D
T 10K In accordance with
DIN EN 255
- Heating output
- Power consumption
- Output figure/coefficient
of performance COP
B0/W55
D
T 5K In accordance with
DIN EN 14511
- Heating output
- Power consumption
- Output figure/coefficient
of performance COP
kW
kW
-
kW
kW
-
kW
kW
-
22,00
5,00
4,40
22,30
4,70
4,60
20,30
6,60
3,10
29,80
6,50
4,60
30,30
6,30
4,80
26,80
8,80
3,00
38,30
8,50
4,50
37,80
8,00
4,70
36,20
11,70
3,10
45,90
10,00
4,60
45,50
9,70
4,70
42,30
14,10
3,00
Interior noise level
(B0/W35 in accordance with EN 12102)
dB(A)
63
63
63
65
Installation location
- permitted ambient temperature
°C
Interior/dry
7 - 25
Application limits
At the same volume flow rates as for
the nominal output test under standard
nominal conditions with nominal vol-
ume flow rates and a spread of
D
T 3K in
the brine circuit and
D
T 5K in the heat-
ing circuit
B-10/W25
B-10/W55
B-5/W62
B20/W62
B20/W25
Operation of the pump outside the application limits results in the heat pump
being switched off by the internal control and safety installations.
14.1 Technical Data VWS