4 Operation

6

Operating instructions

multiMATIC

0020255037_00

3.2.4

Hot water generation

A temperature sensor measures the temperature of the wa-
ter in the domestic hot water cylinder and forwards the val-
ues to the control. At a low domestic hot water temperature,
the control increases the temperature in the domestic hot
water circuit and thus heats the water in the domestic hot
water cylinder to the set domestic hot water temperature.

3.2.5

Circulation

If a circulation pump is installed in the heating installation,
the draw-off points will provide hot water more quickly. The
circulation pump pumps hot water through the secondary
return pipes in the circuit and to the draw-off points.

3.3

Zones

A building is divided into several zones if the heat demand
differs between different sections of the building.

If underfloor heating and radiator heating are installed in
a house.

If a house contains more than one independent residen-
tial unit.

If more than one zone is available, the controller controls the
available zones.

3.4

Hybrid manager

If you have connected a heat pump, the hybrid manager
attempts to cover the declared energy requirement under
the considerations of the cost optimisation and the technical
conditions.

Note

To ensure that the heat pump and the boiler can
work effectively and in synch with one another,
the tariffs (

Page 15) must be set correctly. If

the tariffs are set incorrectly, this may result in
increased costs.

If the system declares an energy requirement, the hybrid
manager switches on and forwards the energy requirement
to the heat generator. The hybrid manager decides which
heat generator to operate based on the tariffs that are set in
relation to the energy requirement.

3.5

Frost protection function

The frost protection function protects the heating system and
apartment from frost damage. The frost protection function
monitors the outside temperature.

If the outside temperature

falls below 4 °C, the controller switches the heat gener-
ator on after a frost protection delay time, and brings the
target room temperature to 5 °C.

rises above 5 °C, the controller does not switch the heat
generator on but monitors the outside temperature.

Note

The competent person can set the frost protection
delay time.

3.6

Preventing malfunctions

Ensure that air can circulate freely around the controller,
and that the controller is not covered by furniture, cur-
tains or other objects.

Ensure that all radiator valves in the room where the con-
troller is fitted are fully open.

3.7

Identification plate

The identification plate is located inside the product and is
not accessible from the outside.

3.8

Serial number

You can call up the serial number to the display under

Menu

Information

Serial number

. The 10-digit article number

is located in the second line.

3.9

CE label

The CE label shows that the products comply with the basic
requirements of the applicable directives as stated on the
identification plate.

The declaration of conformity can be viewed at the manufac-
turer's site.

4

Operation

4.1

Operating structure

4.1.1

Adjustment and display levels

The product has two adjustment and display levels.

The end user level contains information and setting options
that you require as the end user.

The installer level is reserved for the competent person. It is
protected by a code. Only competent persons may change
any settings in the installer level.

Operating levels (

Page 21)

4.1.2

Menu structure design

The menu structure consists of several selection levels and a
setting level.

You can always use the selection button

Menu

to access

selection level 1 from the basic display.

You can use the selection button

Op. mode

to directly ac-

cess the setting level

Operating mode

.

The lowest level is always the setting level.

Summary of Contents for multiMATIC VRC 700

Page 1: ...perating instructions multiMATIC VRC 700 5 BE fr CH fr FR Publisher manufacturer Vaillant GmbH Berghauser Str 40 D 42859 Remscheid Tel 49 21 91 18 0 Fax 49 21 91 18 2810 info vaillant de www vaillant de ...

Page 2: ...al number 6 3 9 CE label 6 4 Operation 6 4 1 Operating structure 6 4 2 Basic display 7 4 3 Operating concept 8 5 Operating and display functions 10 5 1 Information 10 5 2 Settings 12 5 3 Operating modes 16 5 4 Advanced functions 17 5 5 Messages 18 6 Troubleshooting 18 6 1 Temporarily setting limp home mode 18 7 Care 19 7 1 Caring for the product 19 8 Decommissioning 19 8 1 Decommissioning the prod...

Page 3: ...ut by children unless they are supervised Any other use that is not specified in these instructions or use beyond that specified in this document shall be considered improper use Any direct commercial or industrial use is also deemed to be improper Caution Improper use of any kind is prohibited 1 3 General safety information 1 3 1 Danger caused by improper operation Improper operation may present ...

Page 4: ...Safety 4 Operating instructions multiMATIC 0020255037_00 contain substances that are hazardous to human health and the environment In this case dispose of the batteries at a collection point for batteries ...

Page 5: ... a weather compensator with an outdoor tem perature sensor that is fitted in the open air The control is connected to the outdoor temperature sensor and the heat generator The control controls the heating installation and other connected components e g the do mestic hot water generation for a connected domestic hot water cylinder or the ventilation of a connected ventilation unit 3 2 1 Heating The...

Page 6: ...protects the heating system and apartment from frost damage The frost protection function monitors the outside temperature If the outside temperature falls below 4 C the controller switches the heat gener ator on after a frost protection delay time and brings the target room temperature to 5 C rises above 5 C the controller does not switch the heat generator on but monitors the outside temperature...

Page 7: ...on of the left hand selection button 7 Desired setting 8 Symbol for Auto operat ing mode 9 Mode for the current operating mode The basic display appears Depending on which level you are in you must press the left hand selection button several times If the control is in a selection level or setting level and you do not operate the control for more than 5 minutes 4 2 1 Preferred zone in the basic di...

Page 8: ...he control becomes inoperative and dashes appear on the display instead of values If you do not operate the controller during a period of more than 5 minutes the basic display appears again 4 3 1 Using the rotary knob to make settings in the basic display If the display shows the basic display you can use the rotary knob to change the desired setting The setting that you change depends on the sele...

Page 9: ...he left hand selection button Menu The controller switches to selection level 1 Menu Information Desired temperatures Timer programmes Back Select 3 Turn the rotary knob until the list entry Basic settings is highlighted Menu Planning days away from home Planning days away from home Days at home scheduling Basic settings Basic settings Back Select 4 Press the right hand selection button Select The...

Page 10: ... the heating installa tion s operating mode Standby The heating installation has no energy require ment and is in standby Heat mode The heating installation heats the living areas to the Desired heating temp Cooling The heating installation cools the living areas to the Desired cooling temp DHW The heating installation heats the hot water in the cylinder to the desired temperature Domestic hot wat...

Page 11: ...hat is displayed and the actual energy consumption or energy yield may be significant The specifications for the energy consumption or energy yield are not suitable to be used to create or compare energy billing 5 1 2 1 Consumption Some components do not support the calculation of con sumption the total of which is shown on the display In the instructions for the components you can find out if and...

Page 12: ...played in the top right 5 1 3 Read competent person contact details Menu Information Contact details If the competent person entered their company name and telephone number when they installed the product you can read this data under Contact details 5 1 4 Reading the serial number and article number Menu Information Serial number Serial number shows the serial number of the control ler which the c...

Page 13: ...he time periods the controller brings the room tem perature to the set Set back temp heat 5 2 3 4 Setting time programmes quickly If for example you require different time periods for just one working day in the week first set the times for the entire block Monday Friday Then set the different time period for the working day 5 2 3 5 Displaying and changing different times in the block Monday Sunda...

Page 14: ...y offers one tariff you do not need to set any time periods The cost for the electricity is calculated using one tariff Setting costs Page 15 5 2 4 Days away from home scheduling Menu Days away from home scheduling You can use this function to set a period of time and a temperature for the days that you are away from home System operation during the set time period The hot water is not being heate...

Page 15: ...ed display You can use this function to choose whether you see the data for heating cooling or ventilation in the basic display 5 2 12 Setting costs You must specify all tariffs in the unit of currency per kWh for the calculation to be correct If your energy supply company specifies the gas and elec tricity tariff in the unit of currency per m 3 ask for the precise gas and electricity tariff in th...

Page 16: ... activated directly from any operating mode using the right hand selection button Op mode If the heating installation is equipped with more than one zone the activated operating mode only applies for the zone that was preset by the competent person If more than one zone is activated you can set a separate operating mode for each zone using the left hand selection button Menu Basic settings The pat...

Page 17: ...t operating mode 5 4 Advanced functions The advanced functions can be activated directly from any operating mode using the right hand selection button Op mode If the heating installation is equipped with more than one zone the activated advanced function only applies for the zone that was preset by the competent person If more than one zone is activated you can set a separate advanced function for...

Page 18: ...s a mainten ance message in the display To prevent the heating installation from breaking down and to prevent damage you must pay attention to the mainten ance message If the operating instructions for the unit that is shown con tain a maintenance instruction regarding the maintenance message carry out the maintenance work in accordance with the maintenance instruction If the operating instruction...

Page 19: ... être montée dans un de nos appareils la garantie Vaillant se verait automatiquement annulée 3 Afin que la garantie puisse prendre effet la fiche de garantie dûment complète signée et affranchie doit nous être retournée au plus tard quinze jours après l installation La garantie n est pas d application si le mauvais fonc tionnement de l appareil serait provoqué par un mauvais réglage par l utilisat...

Page 20: ...illant sont raccordés dimensionnement du produit inapproprié aux cara ctéristiques de l installation conditions de transport ou de stockage inappropriées usage anormal des produits ou des installations auxquelles ils sont reliés dysfonctionnement d une pièce de rechange non com mercialisée par le constructeur environnement inapproprié au fonctionnement normal des produits en ce compris caractérist...

Page 21: ...ive A 2 End user level The description of the functions for ZONE1 also applies for all available zones Setting level Values Unit Increment select Default setting Min Max Information System status System Fault status Current value No fault Fault list Green IQ Off On On Water pressure Current value bar System status Current value Standby Heat mode Cool ing DHW Burner Current value On off Collector t...

Page 22: ...e last month kWh Fuel Total value for the last month kWh Hot water Electricity Total value since start up kWh Fuel Total value since start up kWh Information Consumption History Heating Electricity Total value since start up kWh Fuel Total value since start up kWh Hot water Electricity Total value since start up kWh Fuel Total value since start up kWh Information Solar yield Bar chart Previous yea...

Page 23: ...pending on the ventilation unit Time programmes ZONE1 Heating Time programmes ZONE1 Cooling Time programmes Circulation Time programmes Ventilation Individual days and blocks Monday Tuesday Wednes day Thursday Friday Sat urday Sunday and Monday Friday Saturday Sunday Monday Sunday Mo Fr 06 00 22 00 Sa 07 30 23 30 Su 07 30 22 00 Period 1 Start End Period 2 Start End Period 3 Start End 00 00 24 00 h...

Page 24: ...ear 01 01 15 Time 00 00 23 59 h min 00 10 08 00 Daylight saving time Manual Auto Manual Basic settings Display Display contrast 1 15 1 9 Button lock off On off Preferred display Heating Cooling Vent Heating Basic settings Costs Tariff for aux heater 1 999 1 12 Low tariff elec rate 1 999 1 16 High tariff elec rate 1 999 1 20 Basic settings Offset Room temperature 3 0 3 0 K 0 5 0 0 Outside temperatu...

Page 25: ...ew Restricted opera tion comfort protection insuf ficient heating up of the heating and the domestic hot water Heat pump does not work 1 Inform the competent person 2 Select the setting for limp home mode until the competent person arrives 3 Read the Temporarily setting limp home mode Page 18 function for more details Display view Fault F Fault Heat generator 1 the specific fault code e g F 33 and...

Page 26: ...he operating instructions for the ventilation unit 4 Low water pres sure The water pressure in the heat ing system is too low Refer to the operating instruc tions for the relevant heat gen erator for information on filling with water See the operating instructions for the heat generator 5 Service date Next service on The competent person has entered a date on which main tenance is due for the heat...

Page 27: ...splay 7 Outside temperature setting the offset 15 P Party 18 Preventing a malfunction 6 R Reading the article number 6 12 Reading the electrical consumption 12 Reading the environment yield 12 Reading the fuel consumption 12 Reading the heat recovery yield 12 Reading the serial number 6 12 Reading the solar statistics 12 Reading the system status 10 Restoring the language 14 Room temperature setti...

Page 28: ...0255037_00 T Time period deviating times in the block 13 Time programme quick setting 13 Setting 13 Time programme after switching off the voltage 13 V Ventilation 5 Ventilation boost 18 Ventilation level 12 Z Zone 6 12 Zone in the basic display 7 ...

Page 29: ......

Page 30: ......

Page 31: ......

Page 32: ...ntendienst 2 3349352 info vaillant be www vaillant be Vaillant Sàrl Rte du Bugnon 43 CH 1752 Villars sur Glâne Tél 026 40972 10 Fax 026 40972 14 Service après vente tél 026 40972 17 Service après vente fax 026 40972 19 romandie vaillant ch www vaillant ch N V Vaillant S A Golden Hopestraat 15 B 1620 Drogenbos Tel 2 3349300 Fax 2 3349319 Kundendienst Service après vente Klantendienst 2 3349352 info...