7 Troubleshooting
42
Installation instructions recoVAIR 0020236694_04
–
See the operating instructions for
the control or for the remote con-
trol.
7 Troubleshooting
Conditions
: Ventilation units do not work
▶
Switch off the product.
▶
Ensure that the fan unit is correctly
mounted on the wall-mounting frame
and the contact for the plug connection
has been established.
Conditions
: Products that are connected down-
stream of the MASTER in the system cannot be
configured as SLAVES during start-up, but rather
as MASTERs
▶
Switch off all of the products in the sys-
tem.
▶
Ensure that the fan unit is correctly
mounted on the wall-mounting frame
and the contact for the plug connection
has been established.
▶
Start up the product again (
→
section
"Start-up").
Conditions
: The remote control and MASTER do
not communicate with each other
▶
Shorten the radio link to less than 15 m.
Conditions
: Ventilation units only work in night
mode
▶
Ensure that the MASTER is not
covered.
8 Repair
8.1 Procuring spare parts
The original components of the product
were also certified by the manufacturer as
part of the declaration of conformity. If you
use other, non-certified or unauthorised
parts during maintenance or repair work,
this may void the conformity of the product
and it will therefore no longer comply with
the applicable standards.
We strongly recommend that you use ori-
ginal spare parts from the manufacturer as
this guarantees fault-free and safe opera-
tion of the product. To receive information
about the available original spare parts,
contact the contact address provided on
the reverse of these instructions.
▶
If you require spare parts for mainten-
ance or repair work, use only the spare
parts that are permitted for the product.
8.1.1 Replacing the fan unit and front
panel
1. Switch off the product.
A
B
C
2. Remove the fan unit.
3. Remove the wind guard and front
panel from the fan unit.
4. Replace the fan unit and the front
panel.
5. Install the wind guard and front panel
on the fan unit.
6. Install the fan unit with wind guard and
front panel.
Summary of Contents for recoVAIR VAR 60/1 D
Page 11: ...客户服务 11 0020236694_04 recoVAIR 安装说明 9 11 客户服务 客户服务的联系信息请参见附件 Country Specifics 或者我们的网站 ...
Page 174: ......
Page 175: ......