Split Type Installation Manual
25
EN
Check if the resistance value of sensor
is abnormal.
Replace the sensor
Check if the circuit of sensor is open or short;
pins are not well connected;
sealing off or rosin join on the PCB
Correct the error
YES
N
O
Components on PCB are broken.
Replace the PCB
YES
7.2
Diagnosis and solution for V12-multi model
060-M2W
Service Diagnosis 7
E2
Indoor environment temperature sensor fault
E2 error diagnosis and solution:
N
O
Check if the resistance value of sensor
is abnormal.
Replace the sensor
Check if the circuit of sensor is open or short;
pins are not well connected; sealing off or rosin
join on the PCB
Correct the error
YES
N
O
Components on PCB are broken.
Replace the PCB
YES
E3
Indoor coil temperature sensor error
E3 error diagnosis and solution:
N
O