VAM 6 MWN-I_EN - 09/14 - Vaillant
25
Cooling
Energy label
YES
YES
YES
Pdesign
kW
5,00
8,00
8,00
SEER
5,60
5,10
5,10
Annual energy consumption
kWh
313
549
549
Heating
(Average
climate)
Energy label
YES
YES
YES
Pdesign
kW
4,60
7,00
7,00
SCOP
3,80
3,80
3,80
Annual energy consumption
kWh
1695
2579
2579
Required back up heating cap at design conditions kW
1,5
1,600
1,600
Cooling
A Condition (35°C - 27/19)
Pdc kW
5,139
7,568
7,598
EERd
3,410
2,901
2,950
B Condition (30°C - 27/19)
Pdc kW
3,695
5,308
5,671
EERd
4,870
4,603
4,160
C Condition (25°C - 27/19)
Pdc kW
2,159
3,588
3,497
EERd
7,340
6,557
5,890
D Condition (20°C - 27/19)
Pdc kW
2,030
3,371
3,150
EERd
10,860
8,764
8,630
Heating
(Average
climate)
TOL
Tol (temperature operating limit)
°C
-10°C
-10°C
-10°C
Pdh (declared heating cap)
kW
3,859
5,272
5,464
COPd (declared COP)
2,600
1,880
1,930
TBivalent
Tbiv (bivalent temperature)
°C
-7°C
-7°C
-7°C
Pdh (declared heating cap)
kW
4,219
5,641
5,710
COPd (declared COP)
2,740
2,245
1,930
A Condition
(-7°C)
Pdh (declared heating cap)
kW
4,219
5,641
5,710
COPd (declared COP)
2,740
2,245
1,930
B Condition
(2°C)
Pdh (declared heating cap)
kW
2,666
3,572
3,443
COPd (declared COP)
3,770
3,669
3,760
C Condition
(7°C)
Pdh (declared heating cap)
kW
1,647
2,459
2,615
COPd (declared COP)
4,830
4,720
5,070
D Condition
(12°C)
Pdh (declared heating cap)
kW
1,834
2,794
2,588
COPd (declared COP)
6,130
5,446
6,050
Pto (Thermostat off) (Cooling/Heating)
kW
0.051 / 0.019
0.096 / 0.012
0.099 / 0.017
Cooling
Psb (Standby mode cooling)
kW
0,005
0,008
0,008
Pcycc
kW
N.A.**
/
N.A.**
EERcyc
N.A.**
/
N.A.**
Cdc (Degradation cooling)
0,250
0,250
0,250
Pck (Crankcase heater mode)
kW
0,000
0,000
0,000
Poff (Off mode)
kW
0,005
0,012
0,008
Heating
Psb (Standby mode heating)
kW
0,005
0,008
0,008
Pcych
kW
N.A.**
/
N.A.**
COPcyc
N.A.**
/
N.A.**
Cdh (Degradation heating)
0,250
0,250
0,250
Table 14
Additional datasheet.
*
Not available.
** We have different sound level datas according to different air flow volume
or frequencies, not according to the working temp.
i
NOTE!
As part of its policy for ongoing improvements of
its products, Vaillant reserves the right to modify
these specifications without prior notice.
TECHNICAL DATA
EN