Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02
6.5.1
Installing the hot water thermostat mixer
(without secondary circulation line)
2
6
1
4
3
5
Fig. 6.5 Installing the hot water thermostat mixer
(system without secondary circulation line)
Key
1 Non-return
valve
2 Hot water thermostat mixer
3 Hot water pipe
4 Cold mains inlet
5 Expansion relief valve
6 Bivalenter solar cylinder
>
Install a hot water thermostat mixer (
2
) in the hot water
pipe (
3
).
6.5.2 Installing the hot water thermostat mixer
(with secondary circulation line)
230
2
7
10
1
6
5
9
3
4
8
1
Fig. 6.6 Installing the hot water thermostat mixer
(system with secondary circulation line)
Key
1 Non-return
valve
2 Hot water thermostat mixer
3 Solar
controller
4 Hot water pipe
5 Secondary circulation line
6 Circulation pump
7 Contact
thermostat
8 Expansion relief valve
9 Cold mains inlet
10 Bivalent solar cylinder
Where possible, avoid installing a secondary circulation
line, since a secondary circulation line results in higher
energy consumption. If the installation of a secondary
circulation line is required, keep circulation operations to
a minimum by only using circulation mode when
required for demand and temperature reasons.
>
Connect the
secondary
circulation line (
5
) to the hot
water pipe (
4
) via a hot water thermostat mixer (
2
).
6.5.3 Setting the hot water thermostat mixer
a
Danger!
Risk of burns and scalds!
Water at a temperature of more than 60 ºC
can escape from the water draw-off point.
>
Set the hot water thermostat mixer to
less than 60 ºC and check the tempera-
ture at a hot water draw-off point.
>
When commissioning the solar heating system for the
first time, set the hot water thermostat mixer to the
required maximum temperature.
This maximum temperature is observed at the hot water
draw-off points.
6 Installation