71
Installation Instructions VRC 630 0020095108_00
Operating the controller 7
7.3.7 Menu
C11:
Setting the service dates and
access code
Setting the service dates
Service
C11
Telephone
:
Service
01 . 10 . 10
Temperature fault detection
after
Off
> Adjust number
Settable
parameters
Description
Setting range
Factory set-
ting
Phone
Enter your telephone number
When the date for the next service appointment is reached, this
telephone number will be displayed in the 2nd line of the basic
display.
You must set each digit of the telephone number separately. A
maximum of 17 digits is possible.
>
>
0 ... 9, –,
Space
(17-digit)
–
Service
The heating installation must be serviced regularly.
Set the month, day and year for the next service appointment.
When the date for the next service appointment is reached,
Ser-
vice
will be displayed in the 2nd line of the basic display.
>
Day
:
1 ... max. 31
(depends on
month)
Month
:
1 ... 12
Year
:
00 ... 99
01.01.01
Temperature fault
detection after
If the flow temperature remains 20% below the calculated target
value for the specified time interval, an error message will be dis-
played for the affected heating circuit.
You activate the temperature fault detection when you set a time
interval.
OFF,
0 ... 12 h
Off
Table 7.19 Settable parameters in Menu C11
Summary of Contents for VRC 630
Page 1: ...GB VRC 630 3 ...
Page 2: ......
Page 54: ......
Page 55: ...For the heating engineer Installation Manual VRC 630 ...
Page 152: ...0020095108_00 GB 022010 Subject to alterations ...