5.6.1
Connecting modulating heating appliances
without eBUS
Fig. 5.14 Connecting a double cascade
If three or more boilers are to be connected, the use of
VR 30 modulating bus couplers is required.
Connect a double cascade directly to the wall mount
(
¬Fig. 5.14
).
eBUS
VR 30
Fig. 5.15 Connecting more than 2 heaters in cascade
If more than two boilers are to be connected in a cas-
cade, a VR 30 modulating bus coupler (accessory) is
required for each boiler.
>
Install the bus coupler directly into the boiler (following
the instructions enclosed with the coupler).
5.6.2 Connecting several modulating heating
appliances with eBUS
eBUS
VR
32
Fig. 5.16 Connecting more than 2 boilers in cascade
Connect the first boiler directly via eBUS.
Pay attention to the correct polarity.
From the 2nd eBUS boiler onwards, use a VR 32
modulating bus coupler for the connection.
i
VR 31, VR 32 and VR 30 bus couplers cannot
be mixed in use.
Use either VR 31 or VR 32 or VR 30 bus couplers
throughout.
Make sure that terminals 7/8/9 on the controller are
not connected to anything.
>
>
>
>
>
43
Installation Instructions VRC 630 0020095108_00
Electrical installation 5