CAB100 analog input channels are not surge protected. Therefore, note the
following:
• The analog input channel wiring must not exceed 30 meters.
• The wiring must not come from outside the building where CAB100 is installed.
If CAB100 cannot be installed in an environment that meets the above criteria, use a
suitable surge protection device that has been installed following local regulations.
CAUTION!
Do not drill holes in the backplate or the enclosure. Drill shavings may
damage the equipment inside the cabinet.
CAUTION!
CAB100 is shipped with a mounting frame and installation accessories for indoor wall
installation. If the screws delivered with the mounting frame are not suitable for the wall
material in the installation location, use any appropriate screws to attach the frame.
CAB100 Installation Guide
M212242EN-B
20