The Galvanic Isolator Wiring Set consist of wiring for 4 devices. Any unused wires in the
Wiring Set have been placed in the cable duct at the factory. If you have, for example,
3 isolators installed on a DIN rail, and want to complete the set by installing a fourth one, use
the existing isolator wires present in the cable duct.
1. De-energize the cabinet:
a. Switch off mains power.
b. Switch off the circuit breaker located inside the cabinet.
1
Circuit breaker
c. Disconnect the galvanic isolator power wire connector from the power block located
on the right-hand side of the cabinet.
2. Remove the cable duct cover above the galvanic isolators.
3. Mount the DL4000 data logger (or loggers), as shown in the following steps.
Each set of 4 galvanic isolators requires a data logger of its own. If you are installing
the second, third, or fourth isolator to complete a set of 4, the steps to mount a new
data logger are not relevant, as you can connect the new isolator(s) to the existing
data logger.
Chapter 6 – Adding devices to CAB100B
87