background image

 

 

 

 

 

 

Quick Reference Guide 

Vaisala CARBOCAP

®

 Carbon 

Dioxide Module GMM112 and 

Transmitter GMW115 

 

–  GMM112 compact diffusion 

aspirated CO

2

 module for OEM 

applications 

– GMW115 

CO

2

 transmitter for wall 

mounting 

–  Measurement range 0 ... 2000 ppm or 

0 ... 5000 ppm CO

2

 

–  Ideal for HVAC applications 

ELECTRICAL CONNECTIONS 

mA 

Signal 4 ... 20 mA 

Signal (+) 0 ... 10 V 

0 Signal 

(-) 

RS-485 Signal B 

RS-485 Signal A 

0 Power 

supply 

(-) 

24V 

Power supply (+) 24 VDC/VAC 

See Figure 3 for wire terminals. 

Powering 

The products require a nominal 24 VDC/VAC power supply 
maintaining a voltage of 18 ... 30 VDC or 20 ... 26 VAC for all 
load conditions and all mains voltages. Although the power input 
includes a half-wave rectifier, it is recommended to use a DC 
supply to avoid current peaks. 

Connections to 24 VAC Power Supply 

Connecting more than one transmitter to a single 24VAC 
transformer forms a common loop and increases the risk of a 
short-circuit. Therefore, a separate floating supply for each 
transmitter is recommended (see Figure 1). 

If several transmitters share a common transformer, the phase (~) 
must always be connected to the 24 V connector in each 
transmitter (see Figure 2). 

 

0601-001 

Figure 1 Connection of Separate AC Supplies (Recommended) 

 

0601-002 

Figure 2 Connection of Single AC supply to Several Transmitters 

MOUNTING AND DIMENSIONS 

Dimensions 

mA

V
0
B
A
0

24V

mA

V
0
B
A
0

24V

25

65

6

30

60

96

Ø3.2

 

0601-004 

Figure 3 GMM112 Module Connections and Dimensions 

66.3

60

60

Ø 4.

2

66.7

85.

3

83.4

85.2

R2.1

124

120.9

25.8

84

R3

.5

 

0601-005 

Figure 4 GMW115 Transmitter Dimensions 

Reviews: