USER'S GUIDE____________________________________________________________________
22 __________________________________________________________________ M211371EN-B
For full configuration options, use the USB service cable and a
terminal program on a PC. Instructions for using the serial line and
the serial commands are provided in Chapter 5, Operation, on page
31.
Selecting the Location
Online dewpoint measurement in still gas is much more demanding
than pressure or temperature measurement. A very tight installation is
crucial: not only pressure tight, but also vapor tight.
It is always best to connect the transmitter directly to the main SF
6
gas volume,
not behind a sampling line
. Avoid extension pipes,
T-pieces, and multi-connection points.
1108-034
Figure 6
Indoor Installation in a Circuit Breaker