background image

HMW70U/Y    
Operating Manual

HMW70U/Y-U191en-1.2

2

1996-08-16

CONNECTION TO AN AC SUPPLY

HMW70U/Y transmitter  

Controller

VAC

VAC

Us

GND

signal

RH/T

GND

Us

RH/T

signal

HMW70U/Y transmitter  

Figure 3: The recommended AC connection

HMW70U/Y transmitter 

HMW70U/Y transmitter  

Controller

shared 

common line

VAC

GND

GND

Us

Us

RH/T

RH/T

signal

signal

Figure 4: A common loop formed in an AC
connection

The HMW70U/Y transmitters can also be
connected to an AC supply without an
external rectifier. However, when more
than one transmitter is connected to one
AC transformer, a common loop is
formed and there is an increased risk of a
short-circuit. To avoid this, use a
separate floating supply for each
transmitter (see Figure 3). However, if
several transmitters have to share one
transformer, the phase (~) must always
be connected to U

connector in each

transmitter (see Figure 4).

ONE-POINT RH CALIBRATION

The accuracy is recommended to be
checked at least once a year; the interval
depends on the operating conditions and
the required accuracy of the
measurement. When checking the
transmitter calibration, use the HMI41
indicator provided with an appropriate
probe and optional calibration cable. If
adjustment is necessary, use the humidity
offset potentiometer.

REPLACEMENT OF THE HUMICAP
SENSOR

Remove the damaged sensor and insert a
new one. Handle the sensor by the plastic
socket. Recalibrate the transmitter.

Summary of Contents for Humicap HMD60U

Page 1: ...n can be conveniently performed on site with the HMI41 indicator equipped with an appropriate probe and optional calibration cable Figure 1 Dimensions of the HMD60U Y GROUNDING If the cable diameter i...

Page 2: ...ET T TEST 1 2 3 4 5 mA TEST RH mA mA mA or or Figure 3 Electrical connections Signal cables are connected to a removeable 5 pole screw connector Make the connections according to Figure 3 above RH tes...

Page 3: ...racy is recommended to be checked at least once a year the interval depends on the operating conditions and the required accuracy of the measurement The transmitter calibration can be conveniently che...

Page 4: ...ing cast aluminium Cable lead through bushing for 7 10 mm PG9 cable housing IP65 NEMA 4 part no 18941HM or armoured cable glands part no 10528HM Sensor protection standard membrane filter part no 1703...

Page 5: ...RH T X3 X4 UP wet dry HUMICAP sensor sensor Figure 2 Electrical connections Signal cables are connected to a removeable 5 pole screw connector Make the connections according to Figure 2 110 4 33 85 3...

Page 6: ...ge temperature range 40 80 C Long term humidity range for electronics 0 85 RH Housing cover ABS plastic base plate PA Connections Screw terminals 0 5 1 5 mm2 Electromagnetic compatibility The emission...

Page 7: ...rformed on site with the HMI41 indicator equipped with an appropriate probe and optional calibration cable GROUNDING If the cable diameter is less than 7mm use a shrinking tube or an adhesive tape cab...

Page 8: ...SUPPLY HMD70U Y transmitter Controller VAC VAC Us GND signal RH T GND Us RH T signal HMD70U Y transmitter Figure 4 The recommended AC connection HMD70U Y transmitter HMD70U Y transmitter Controller s...

Page 9: ...he accuracy is recommended to be checked at least once a year the interval depends on the operating conditions and the required accuracy of the measurement When checking the transmitter calibration us...

Page 10: ...s less than 0 5 RH without recalibration Operating temperature range electronics 5 55 C sensor head 40 80 C Storage temperature range 40 80 C Housing sensor head stainless steel electronics housing ca...

Page 11: ...te the UP sign which shows the correct mounting position Be careful not to damage the HUMICAP 180 sensor ELECTRICAL CONNECTIONS AND CALIBRATION POTENTIOMETERS RHout Tout Us GND T RH 0 1V 0 5V RH T T R...

Page 12: ...s an increased risk of a short circuit To avoid this use a separate floating supply for each transmitter see Figure 3 However if several transmitters have to share one transformer the phase must alway...

Page 13: ...rs connections An output change causes an error which is less than 0 5 RH without recalibration Operating temperature range 5 55 C Storage temperature range 40 80 C Long term humidity range for electr...

Reviews: