Register Number
(Decimal)
Address
(Hexadecimal)
Register
Description
Data Format
Bit Order
14
000D
hex
Gas level ROC
caution alerts for
one month
average values
16-bit field
0 = Methane
1 = Acetylene
2 = Ethylene
3 = Ethane
4 = Carbon
monoxide
5 = Carbon
dioxide
6 = TDCG
7 = Hydrogen
15
000E
hex
Gas level alarms
for present values
16-bit field
0 = Methane
1 = Acetylene
2 = Ethylene
3 = Ethane
4 = Carbon
monoxide
5 = Carbon
dioxide
6 = TDCG
7 = Hydrogen
8 = Moisture in oil
9 = Relative
moisture in oil
16
000F
hex
Gas level ROC
alarms for 24h
average values
16-bit field
0 = Methane
1 = Acetylene
2 = Ethylene
3 = Ethane
4 = Carbon
monoxide
5 = Carbon
dioxide
6 = TDCG
7 = Hydrogen
OPT100 User Guide
M211858EN-E
66