Delays in a VaiNet Network
VaiNet protocol and VaiNet devices are designed for power-efficient operation. Some of the
design choices that enable long battery life also create significant delays that the users should
be aware of.
Intermittent Radio Connections
Radio connections between VaiNet access points and data loggers are not continuous. Access
points take turns communicating in a two-minute cycle, and connected data loggers send their
measurement data to their connected access point every four minutes. This introduces various
delays:
• Data loggers that are not currently connected (new devices or ones that have fallen out of
radio contact) have to scan for available access points for a complete cycle before they
can decide what is the optimal access point for them. This means that connection
attempts typically take at least a couple of minutes. Additionally, some joining scenarios
may take multiple attempts. For example, when filling a single access point up to its full
capacity of 32 data loggers, it may take an hour for the last data logger to successfully
connect to the access point.
• Access points request missing data and issue management commands to data loggers
within their communication window. Transferring a full month's worth of measurement
data from 32 data loggers using one access point takes several hours.
Data Logger Scanning Interval
Scanning for available access points consumes power. To prevent repeated scanning from
draining their batteries, RFL100 Data Loggers shut down their radio temporarily if they can
find no access points to join. They will resume scanning after a waiting interval that gets
progressively longer if they keep failing to find an access point. The maximum interval is 8
hours and 30 minutes.
This means that when access points become available after an outage, it may take several
hours for data loggers to discover them. This is why you should always keep your access points
powered up, and why you should start your network installation by installing the viewLinc
Enterprise Server and access points first.
You can manually wake up the radio of an RFL100 Data Logger by pressing its
Refresh
button. The button is located next to the service port under the silicone
plug.
More Information
For more information on AP10 Access Point, see
AP10 User Guide (M211860EN)
available at
.
10
M211821EN-D
Summary of Contents for VaiNet AP10
Page 1: ...EN DE FR ES PT ZH M211821EN D Quick Guide Vaisala VaiNet Wireless Access Point AP10...
Page 3: ...Table of Contents English 5 Deutsch 13 Fran ais 21 Espa ol 29 Portugu s 37 45 3...
Page 4: ...4 M211821EN D...
Page 47: ...AP10 B A 31 AP10 A 2 B 4 116 4 57 124 4 88 3 50 0 11 mm in 32 AP10 1 AP10 2 6 2 47...
Page 52: ...Vaisala helpdesk vaisala com www vaisala com support www vaisala com warranty 52 M211821EN D...
Page 53: ......
Page 54: ...www vaisala com...