Page 38
Installation and Operation Manual - FP18 Dallaire
ENGLISH
8.6.2 Option #2 - Raised Base Installation of Less Than 4"
When the fireplace is installed on a
raised base of Less Than 4"
(E)
, a non-
combustible floor protection of at least
16"
(A)
with an R factor of 1.00 must
be installed in front of the fireplace.
The joint between the floor protection
and the fireplace must be protected over
the entire width of the floor protection
by a folded and continuous metal sheet
(D = min 2" [51 mm]) (not supplied).
It is recommended to make the sheet
metal in one piece.
A clearance of 80" (2.03 m)
(F)
between
the base of the fireplace and the ceiling
must be respected.
8.6.3 Option #3 - Raised Base Installation of 4" or More
When the fireplace is installed on a
raised base of 4" or more
(E)
, a non-
combustible floor protection of at least
16"
(A)
with no R factor must be installed
in front of the fireplace.
The upper and lower angle, for the
full width of the floor protection, must
be protected by 2" horizontally and
vertically by a folded and continuous
metal sheet (D = 2" [51 mm])
(not supplied). The sheet metal does
not have to cover the rest of the wall
between the base of the fireplace and
the floor. A clearance of 80" (2.03 m)
(F)
between the base of the fireplace and the
ceiling must be respected.
D
D
E
A
E
F
E
F
D
D
D
D
E
A