- 56 -
User setting
High Temperature Antisepsis Function: (when hot water function is selected)
◎
High temperature Antisepsis cycle is once every 7 days
(
Cancel this function when the
selection is 0
)
;
◎
When entering the high temperature Antisepsis, the water tank electric heater will be
forced to turn on.
◎
During the Antisepsis process, if the water tank temperature > 60
℃
(the maximum
settable temperature), then the compressor will not start, but only start electric heating; if
the water tank temperature
≤55
℃
, both the compressor and electric heater will start.
◎
When the water tank temperature
≥70
℃
and the protection temperature lasts for
30minutes
≥65
℃
, exit the high temperature Antisepsis.
◎
After entering high temperature Antisepsis, if the temperature of the hot water tank does
not reach 65°C after 1 hour, the high temperature Antisepsis program will be forced to exit.
Target Temperature Auto Adjustment Logic ( Under Heating Mode)
◎
The target temperature under heating mode can be automatically adjusted according to
the ambient temperature.
◎
Entry conditions
When Parameter enables automatic adjustment mode of heating target temperature.