Calculation formula of heating target temperature
Pset (heating target temperature) =20
℃
+ (Target temperature compensation coefficient
÷
10) * (Heating compensation temperature point - current ambient temperature)
◎
The above different curves stands for the different value of Target temperature
compensation coefficient.
(When Target temperature compensation coefficient=1, the actual value is 0.1)
◎
The target temperature range of automatic temperature adjustment is 20-60
℃
Auxiliary Electric Heater for Water Tank
◎
Start conditions (all below conditions must be met at the same time)
1) In hot water mode;
2) The compressor runs for start time for electric heating of water tank
(
30
)
minutes;
3) There is a demand for hot water, and the temperature of the water tank is ≤55
℃
;
4) The pump is running
◎
Exit condition (only need to meet any one of the below conditions)
1) When the heat pump is performing cooling mode / hot water mode;
2) When there is no demand for hot water or constant temperature control;
3) The water tank temperature sensor has a fault alarm;
◎
When it is under defrosting / forced defrosting / secondary antifreeze , the electric heating is
forced to turn on;