background image

505

REVO-E Heat pump

5 Troubleshooting

Actions

Measured values on sensor NOK => replace sensor

Measured values on cable harness (SC620 side) 
NOK => inspects pin / replace cable harness

Measured values on cable harness (SC620 side) OK 
=> replace SC620

F08 Temperature of air duct / outlet temperature too 
low (T<= -40°C) 

System behavior

Limited heating functionality

Necessary inspections

Sensor values using DCT

Sensor resistance on the sensor / to the SC620 plug 
(SC620 not connected) according to wiring plan

10kOhm 12.5kOhm

15.7kOhm

25°C

20°C

15°C

Voltage present on sensor when SC620 and sensor 
plug connected

1.36V

1.5V

1.7V

25°C 20°C

15°C

Actions

Measured values on sensor NOK => replace sensor

Measured values on cable harness (SC620 side) 
NOK => inspects pin / replace cable harness

Measured values on cable harness (SC620 side) OK 
=> replace SC620

F09 Temperature of recirculated air / passenger cabin 
too high (T

 105°C) 

System behavior

Limited heating functionality

Limited cooling functionality

Necessary inspections

Sensor values using DCT

Sensor resistance on the sensor / to the SC620 plug 
(SC620 not connected) according to wiring plan

10kOhm

12.5kOhm

15.7kOhm

25°C

20°C

15°C

Voltage present on sensor (SC620 / sensor plug con-
nected)

1.36V

1.5V

1.7V

25°C 20°C

15°C

Actions

Measured values on sensor NOK => replace sensor

Measured values on SC620 plug NOK => inspect pins 
/ replace cable harness

Measured values on cable harness SC620 side OK 
=> replace SC620

F10 Temperature of recirculated air / passenger cabin 
too low (T<= -40°C) 

System behavior

Limited cooling functionality

System in Cooling Mode

Necessary inspections

Sensor values using DCT

Sensor resistance on the sensor / to the SC620 plug 
(SC620 not connected) according to wiring plan

10kOhm 12.5kOhm

15.7kOhm

25°C

20°C

15°C

Voltage present on sensor (SC620 / sensor plug con-
nected)

1.36V

1.5V

1.7V

25°C 20°C

15°C

Actions

Measured values on sensor NOK => replace sensor

Measured values on SC620 plug NOK => inspect pins 
/ replace cable harness

Measured values on cable harness SC620 side OK 
=> replace SC620

F11 Sensor value high pressure implausible high 
(evaluation of sensor signal) 
(measured value Pabs > 26bar)

System behavior

Error occurs after multiple switching of the high-pres-
sure safety switch 

only in combination with F18

In Cooling Mode:

default value high pressure 20bar

axial fans maximum speed

In Heat Pump Mode:

radial blowers maximum speed

compressor minimum speed

Necessary inspections

Sensor values using DCT

Check pressure with pressure gauge and calibrate 
with sensor values
(Attention: sensor values are absolute values)

Sensor resistance 5.4kOhm on the sensor / to the 
SC620 plug (SC620 not connected) according to 
wiring plan when compressor has not been function-
ing for long period of time

Voltage present on sensor (SC620 / sensor plug con-
nected) when system running

~7.4bar ~6.4bar
1.36V

1.5V 

When compressor has been off for a longer time
1.7V at 15°C

Summary of Contents for REVO-E

Page 1: ...Rev 06 2019 Id No 11123006A REVO E Heat pump Volvo Workshop Manual AIR CONDITIONING...

Page 2: ...nctional schematic of the REVO E heat pump 402 4 3 Functional schematic of the REVO E heat pump Volvo 7900 Electric 403 4 4 Work modes of the REVO E heat pump in the Volvo 7900 Electric 404 4 4 1 Heat...

Page 3: ...701 7 4 Inspection and maintenance 701 7 4 1 Changing the fresh air filter 701 7 4 2 Changing the filter dryer 701 7 4 3 Inspecting the oil level of the compressor 702 7 4 4 Changing the compressor o...

Page 4: ...7 9 9 1 Remove the duct temperature sensor blow out temperature 907 9 9 2 Install the duct temperature sensor blow out temperature 907 9 9 3 Remove the recirculating air suction temperature sensor pas...

Page 5: ...mage NOTE Is used when something is to be emphasized 1 4 Symbols 1 5 Additional documentation to be used The use of additional servicing literature is required This is indicated in the workshop manual...

Page 6: ...rk if the motor is still and the 24V DC power supply as well as the high voltage has been switched off Before starting work on the air conditioning system ensure that the system is voltage free and ma...

Page 7: ...her temperatures mean higher pressures which may lead to the container exceeding its maximum allowed pressure The rules for pressurized containers stipulate that containers are not to be warmed beyond...

Page 8: ...Hybrid global chassis application HGA Hei gasabtauung Hot Gas Deicing HV Hochvolt High Voltage HVAC Heizen L ften Klima Heating Ventilation Air Conditioning HVIL High Voltage Interlock Loop High volt...

Page 9: ...s 1st Generation till 2018 Operating range heat pump C 5 3 Cooling capacity kW 1 25 Heating capacity in heat pump mode kW 2 16 Heating capacity coolant circuit kW 40 Air volume m h 6960 Current consum...

Page 10: ...bb 1 REVO E HP Installation variants REVO E HP HP Zone 1 For connection to front box REVO E HP 11120816_ 1st generation on solobuses REVO E HP 11123865_ 2nd generation on solobuses und articulated var...

Page 11: ...valve suction side 16 Expansion valve heating circuit heat pump 17 Safety valve 30bar 18 Bracket refrigerant compressor 19 Refrigerant collector 20 Refrigerant compressor 21 Refrigerant charging valve...

Page 12: ...mponents 400V AC 600V DC Fig 3 Overview of high voltage cable harnesses components 400V AC 600V DC 1 High voltage power supply of the frequency converter 600V DC 2 High voltage power supply of the com...

Page 13: ...harness axial fan 4 way reversing valve 6 solenoid valve hot gas deicing in 11123865_ only 7 wiring harness kit 400V AC frequency converter 8 PE connection compressor 9 compressor 10 suction pressure...

Page 14: ...cessary discharge refrigerant flow required for cooling The compressor is integrated into the air conditioning system The compressor with patented vibration decou pling design is created using a speci...

Page 15: ...olute Central parameters for climate heat pump control recognizing icing recognizing low pressure High pressure The high pressure sensor determines the pressure level in the permanent high pressure ar...

Page 16: ...EVO E Explanations in the following chapters refer largely to the new functions of the heat pump The intelligent controller logic of the SC620 controls further the entire system It communicates with t...

Page 17: ..._AuxiliaryPowerEnable and supply Fig 401 Functional schematic of the REVO E Analog input HVIL 1 voltage Analog input HVIL 2 voltage CAN interface vehicle SC620 Sensor blow out temperature Sensor pass...

Page 18: ...radial blowers In Cooling Waste Energy or Gas Charging Mode the double radial blowers are controlled by the SC620 Fig 402 Functional schematic of the REVO E internal Analog input HVIL 1 voltage Analo...

Page 19: ...heat Mode 8 Waste Energy Mode 9 Gas Charging Mode new mode for heat pump in 11123865_only This is a list of priorities in case several modes are simul taneously required by the BEA body system The SC6...

Page 20: ...ig 403 Heating and Ventilation Mode HV Mode Double radial blower Double radial blower Fresh air flaps Sensor pass comp temperature Sensor blow out temperature I O A module Vehicle Requirement open clo...

Page 21: ...lation Mode Ready for Cooling Double radial blower Double radial blower Fresh air flaps Sensor pass comp temperature Sensor blow out temperature I O A module Vehicle Requirement open close Heating val...

Page 22: ...entilation Mode Ready for Heat Pump Double radial blower Double radial blower Fresh air flaps Sensor pass comp temperature Sensor blow out temperature I O A module Vehicle Requirement open close Heati...

Page 23: ...r to cool down the air in the passenger cabin to the Delta T value requested by the BEA Body Fig 406 Cooling Mode Analog input HVIL 1 voltage Analog input HVIL 2 voltage CAN interface vehicle SC620 Se...

Page 24: ...mperature to be reached is given by the difference of the external temperature and the T required by the BEA body Example of T 7 Kelvin Tpassenger cabin Texternal 35 C T 7K Tpassenger cabin 28 C This...

Page 25: ...ody D_CabinHeatpumpReq signal sent by BEA body Fig 407 Heat Pump Mode Analog input HVIL 1 voltage Analog input HVIL 2 voltage CAN interface vehicle SC620 Sensor blow out temperature Sensor pass comp t...

Page 26: ...ol the speed of the double radial blowers axial fans Activation and speed setting of the compressor via frequency converter In Heat Pump Mode the BEA body is not able to influence the speed of the dou...

Page 27: ...ailable to BEA body D_CabinHeatpumpReq signal sent by BEA body Fig 408 Operating Mode De Icing Analog input HVIL 1 voltage Analog input HVIL 2 voltage CAN interface vehicle SC620 Sensor blow out tempe...

Page 28: ...2 min and 15 min depen ding on the degree of icing of the outer heat exchanger In order to use the necessary energy for the fastest possible de icing the double radial blowers are switched off during...

Page 29: ...ing in reheat mode is carried out via the water heat exchangers installed in the system The heat pump function can not do this The maximum condenser capacity can be limited by the D_ElAcMaxPowerAllowe...

Page 30: ...aste Energy Mode the air conditioning system attempts to dissipate additional energy from the drive battery This is achieved by running back the efficiency of the air conditioning system e g by reduci...

Page 31: ...ystem is normally not filled when this mode is started and the suction pres sure sensor would therefore read a false value in the vacuum of the system The mode is not part of standard operation and is...

Page 32: ...the heat pump mode as a condenser and the condenser works as an evaporator Additional components such as a modified pipe circuit various check valves and a further expansion valve support the circulat...

Page 33: ...Cooling Mode High pressure area charging phase Low pressure area suction side Liquid phase Outer heat exchanger Inner heat exchanger passenger compartment Expansion valve Filter dryer Receiver Check v...

Page 34: ...Heat Pump Mode High pressure area charging phase Low pressure area suction side Liquid phase Outer heat exchanger Inner heat exchanger passenger compartment Expansion valve Filter dryer Receiver Check...

Page 35: ...pump operation 4 5 3 1 Air conditioning mode See Fig 415 The 4 way reversing valve is in zero position not swit ched The system is working in air conditioning mode 4 5 3 2 Heat Pump Mode See Abb 416...

Page 36: ...421 REVO E Heat pump 4 Function and functional schematics Abb 416 Function of the 4 way reversing valve Heat Pump Mode...

Page 37: ...tside temperature of 5 C Abb 417 Refrigerant circuit function schematic of the heat pump with hot gas de icing 11123865_ High pressure area charging phase Outer heat exchanger Inner heat exchanger pas...

Page 38: ...ances 5 2 3 Why the desired conditions are not reached when testing pressure If deviations from the desired conditions are determined when testing the pressure the following may have caused this Press...

Page 39: ...for these reasons corrosion on the plugs loose contact crimping errors on the plugs or pins corrosion on lines and fuses corrosion on the battery poles damage to the line insulation ATTENTION Search...

Page 40: ...ctive 03 10913 PWM double radial blower defective 04 10914 24V power supply too low 05 11554 External temperature signal not received 10s 06 11555 600V system status not received 10s 07 10917 Temperat...

Page 41: ...nesses according to wiring plan Force control of system via DCT test mode Active with cooling Actions Replace SC620 Replacing double radial blowers NOT necessary F04 24V power supply too low System be...

Page 42: ...s replace cable harness Measured values on cable harness SC620 side OK replace SC620 F10 Temperature of recirculated air passenger cabin too low T 40 C System behavior Limited cooling functionality Sy...

Page 43: ...value 0 5bar compressor off that means below the threshold low pressure error entry F12 F18 Necessary inspections Sensor values using DCT operating 2 bar Check pressure with pressure gauge and calibra...

Page 44: ...ssor does not start Red LED of frequency converter is blinking Note No common problem of the frequency converter Necessary inspections Sensor values using DCT Only relevant in connection with other er...

Page 45: ...entation There are two options for the diagnosis of the frequency converter 1 MMI handheld control device This is sufficient for reading the fault memory but without precise information about the time...

Page 46: ...ntact crimping errors etc and repair as needed Inspect plug contacts for corrosion and proper seat ing repair as needed Visually examine all electric lines high and low volt age for abrasion 5 7 Diagn...

Page 47: ...Lines without color information white Illustrations are generally without power or pressure 6 1 Electrical fuses REVO E Heat Pump 6 2 Wiring diagram REVO E HP 11120816 Fig 601 pages 1 6 includes the w...

Page 48: ...602 REVO E Heat pump 6 Wiring plan Fig 601 Wiring diagram for REVO E HP Sheet 1 These fans will not be used in short run from SP7 and SP8 PWM signal see sheet 5...

Page 49: ...603 REVO E Heat pump 6 Wiring plan Fig 601 Wiring diagram for REVO E HP Sheet 2 from X850 1 and SP7 PWM signal see sheet 5 Condenser cable harness This fan will not be used in short run...

Page 50: ...604 REVO E Heat pump 6 Wiring plan Fig 601 Wiring diagram for REVO E HP Sheet 3 SC600 Interface X133 6 with 10A Fuse SC620...

Page 51: ...605 REVO E Heat pump 6 Wiring plan Fig 601 Wiring diagram for REVO E HP Sheet 4...

Page 52: ...606 REVO E Heat pump 6 Wiring plan Fig 601 Wiring diagram for REVO E HP Sheet 5...

Page 53: ...ndenser Fan PWM 2 Electromagnetic valve Evaporator Blower PWM 3 LP HP Drive Error Fresh Air Flap 4 HVIL detect 1 in Fresh Air Flap 5 HVIL detect 2 out WV 6 Analog Ground Press Sensor WV 7 Pressure Sen...

Page 54: ...608 REVO E Heat pump 6 Wiring plan 6 3 Wiring diagram REVO E HP 11123865 Fig 602 pages 1 6 includes the wiring diagram for the REVO E HP...

Page 55: ...609 REVO E Heat pump 6 Wiring plan Fig 602 Wiring diagram for REVO E HP Sheet 1...

Page 56: ...610 REVO E Heat pump 6 Wiring plan Fig 602 Wiring diagram for REVO E HP Sheet 2...

Page 57: ...611 REVO E Heat pump 6 Wiring plan Fig 602 Wiring diagram for REVO E HP Sheet 3...

Page 58: ...612 REVO E Heat pump 6 Wiring plan Fig 602 Wiring diagram for REVO E HP Sheet 4 In REVO E HP only...

Page 59: ...613 REVO E Heat pump 6 Wiring plan Fig 602 Wiring diagram for REVO E HP Sheet 5...

Page 60: ...ser Fan PWM 2 Electromagnetic valve Evaporator Blower PWM 3 LP HP No Error Fresh Air Flap 4 HVIL detect 1 in Fresh Air Flap 5 HVIL detect 2 out 4WV 6 Analog Ground Press Sensor 4WV 7 Pressure Sensor R...

Page 61: ...00V DC including HVIL connector No Designation Configura tion Cable color 1 L1 DC network Red 2 L3 DC network Blue 3 HVIL in vehicle X61 Pin 1 White 4 HVIL out of vehicle X61 Pin 2 Brown 5 HVIL in sys...

Page 62: ...when connecting the PE line the order of the individual parts must be maintained Fig 605 Fig 604 Voltage output 400V AC 1 Connection for PTC sensor e motor for compressor 2 Cable connection for 400V...

Page 63: ...n 2 Cable gland 3 Cable gland lock nut 4 Position marking cable 5 Phase connections for 400V AC 3 6 Connection for PTC sensor for electrical motor The position marking cable must be secured with lock...

Page 64: ...e air conditioning system and prop up with rods attached to cover Remove the coil of the solenoid valve and replace with permanent magnet Siphon refrigerant via high and low pressure connec tions on t...

Page 65: ...bed in 7 4 Always change the compressor oil when conducting servicing or repair work on the compressor Open the oil filling screw Fig 702 siphon out the old oil and feed in the new oil The amount of o...

Page 66: ...voltage tester CAT IV suitable for HV systems Fig 603 Chap 6 4 8 3 2 Refrigeration section When working on the refrigerant circuit the rules for eva cuating and filling the REVO E apply Replace the s...

Page 67: ...cover remove the grounding cable 2 Disconnect the electrical connections of the frequency converter Check the connections L1 and L3 Fig 603 are voltage free using a suitable voltage tester CAT IV Remo...

Page 68: ...he collar of the plate will dip into opening in the bottom of the heat sink of the frequency converter Inspect the positioning of the centering cone of the fastening screws Attach the frequency conver...

Page 69: ...en lock nuts 3 Fig 606 of the cable glands for the 400V AC cable and pull the cable out of the terminal box Fig 804 exemplarily 1 2 3 4 1 Protective cover of compressor 2 Torx screws 6 3 High pressure...

Page 70: ...hat hold the mounting bracket and remove mounting bracket Separate grounding cable by pulling out ring screws 7 from compressor housing screw ring screws back in 4 Removing compressor Lift compressor...

Page 71: ...ing the air conditioning system see 7 4 4 Note the minimum and maximum oil level Check and adjust as needed the oil level of the air condi tioning system after commissioning 8 4 3 Install the compress...

Page 72: ...s NOTE Please always comply with given torque Other wise the foam will lose its absorbent affect This causes the transference of vibration to the bus roof Install mounting parts of the compressor in t...

Page 73: ...5 2 Install the 600V DC cable Install cable in the opposite order Connecting the clamps see 6 4 ATTENTION The cable must not touch any sharp edges abra sion hazard 8 5 3 Remove the 400V AC cable The c...

Page 74: ...16 Lay the 400V AC cable according to Fig 815 and Fig 817 and attach to the traverses and compressor pan ATTENTION The cable cannot touch any sharp edges abra sion hazard Connect the 400V AC cable to...

Page 75: ...ssor Close openings of components of the refrigerant circuit with suitable plugs presents water absorption by the refrigerant oil Follow up work Exchange filter dryers Evacuation the air conditioning...

Page 76: ...n reverse order Thereby the gaskets of the refrigerant circuit are to be replaced Do the final work according to 9 3 Fig 901 exemplarily 1 Frequency inverter design cover 2 Compressor design cover 3 P...

Page 77: ...902 Positions of expansion valves and the associated contact sensors Contact sensor expansion valve outer heat exchanger Contact sensor expansion valve left hand inner heat exchanger Expansion valve...

Page 78: ...lve 9 4 3 Install an expansion valve Apply refrigerator oil to sealing rings Place the expansion valve 2 into the location of installation and attach with cap nuts Attach thermostat sensor 1 with hold...

Page 79: ...lation and attach with cap nuts While doing so prevent dryer filter from twisting with suitable tool Attach retaining clamp Conduct follow up work according to 9 3 9 6 Receiver removal installation 9...

Page 80: ...ing SCT components test 9 7 3 Remove an axial fan Remove the electrical connection to the housing 4 from the holder 6 Remove attachment screws 5 Remove housing 4 9 7 4 Install an axial fan Insert hous...

Page 81: ...temperature Position to the right side before the first double radial blower 1 Fig 908 Loosen electrical connection on the plug Unscrew sensor from holder 9 9 2 Install the duct temperature sensor bl...

Page 82: ...leak test is 17 bar since otherwise the suction pressure sensor will become damaged 9 11 High pressure sensor removal installation There is a valve insert built into the soldering support of the high...

Page 83: ...Disconnect the pressure line at the SMA connection from the compressor and remove pressure line 9 13 2 Install the pressure line Put pressure line including new seals refrigerator oil applied into ins...

Page 84: ...nut 3 ATTENTION Always ensure the plug points with the cable side down in order to avoid water entry into the plug 9 14 3 Remove the screw in valve Conduct preparation work according to 9 3 Remove co...

Page 85: ...34 10 flange seal oval 11117795A 3 screw M10x110 suction gas line compressor 50 10 flange seal oval 11117795A 4 union nut SW27 outer heat exchanger 25 10 O ring 14 x 1 78 80641A 5 union nut SW27 filte...

Page 86: ...ne 10 10 O ring 4 48 x 1 78 1103522B 12 union nut SW22 expansion valve outlet 25 10 O ring 10 6 x 1 78 80640A 13 union nut SW14 sensor high pressure 10 10 O ring 7 65 x 1 78 80812A 14 union nut SW27 l...

Page 87: ...memos...

Page 88: ...ial Vehicles Germany GmbH Friedrichshafener Str 7 Tel 49 0 8105 7721 0 Fax 49 0 8105 7721 889 82205 Gilching Germany www valeo thermalbus com service valeobus valeo com Valeo Thermal Commercial Vehicl...

Reviews: