background image

3

© Vallox Oy - All rights reserved

USING THE UNIT

The fan speed of the Vallox ventilation unit is adjusted 

using a four-step control.
The available speed options of the control switch  

are 1, 2, 3, and 4:
1.  

Away mode. The ventilation efficiency can be 

temporarily reduced when the apartment is 

unoccupied.

2-3.   Standard mode. In standard mode, the air inside the 

apartment is replaced once every two hours. 

4.  

Boost mode. Cooking, sauna, bathing, drying of 

clothes, guests, and other similar situations can 

require that ventilation be increased from the 

standard setting.

The fan speed can also be controlled through a separate 

Vallox control hood, the Vallox ProControl control panel, 

or directly through voltage messages (0-10 V).

Vallox Simple Control control 

panel

The temperature of the air blown into the apartment can 

be adjusted approximately b10 °C and +30 °C.  

The unit has an automatic summer/winter function  

(a bypass flap).

•  When the adjusted temperature is b10 °C 

and +30 °C, the heat recovery cell is not bypassed, 

i.e. the unit is in winter mode.

•  In the OFF position, the unit is in the summer mode, 

i.e. post-heating is turned off and the heat recovery 

cell is bypassed when the outdoor temperature is 

above +14 °C. The heat recovery will be turned on 

when the outdoor temperature falls below +12 °C.

•  In the AUTO position, the unit will operate as follows 

around the year: The default post-heating setting 

is +17 °C. The unit will bypass the heat recovery cell 

when the temperature of the outdoor air exceeds 

+14 °C. The heat recovery will be turned on when the 

outdoor temperature falls below +12 °C. During the 

bypass, post-heating is turned off.

Adjusting supply air temperature

FAN SPEED ADJUSTMENT

ADJUSTING THE SUPPLY AIR TEMPERATURE  

AND SUMMER/WINTER FUNCTION

The winter function of  

the ventilation unit

The limit value has been set in the factory for freezing of 

the heat recovery cell. When this limit value is exceeded, 

the ventilation unit starts to defrost the heat recovery cell 

by directing the outdoor air past the heat recovery cell.
The duration of the defrost cycle is 15-45 min depending 

on the amount of ice accumulated in the heat recovery cell 

and on the extract air flow. The factory settings ensure 

optimal operation in standard living and detached house 

conditions. Even though the winter operation parameters 

can be adjusted for certain extreme conditions, such as 

swimming pool facilities, it is always advisable to contact 

Vallox maintenance services.

Summary of Contents for 101 MC L

Page 1: ...Manual MANUAL Ventilation unit Document D4686 Valid from 02 10 2017 Updated 12 2 2018 Model Vallox 101 MC R Vallox 101 MC L Type 3740...

Page 2: ...uced sensory physical or mental capabilities or whose lack of knowledge and experience do not ensure safe operation of the unit Such persons can use the unit under supervision or by following the inst...

Page 3: ...the heat recovery cell is bypassed when the outdoor temperature is above 14 C The heat recovery will be turned on when the outdoor temperature falls below 12 C In the AUTO position the unit will oper...

Page 4: ...outdoor air is faulty Check the sensor and the wires replace as required 6 The supply air fan has stopped Check the wiring of the fan re place the fan as required 7 The extract air fan has stopped Ch...

Page 5: ...bient dust concentration It is recommended that the filters be replaced every spring and autumn or at the very least once a year HEAT RECOVERY CELL Check that the heat recovery cell D is clean roughly...

Page 6: ...rille the supply air fan must first be removed from the unit To remove the fan disconnect the quick connector H of the supply air fan T and or the extract air fan P cables Push the fan cables and the...

Page 7: ...ting season begins e g during autumn maintenance check that the condensing water outlets in the bottom pool are not clogged To check this pour some water into the pool Clean as required Water must at...

Page 8: ...rical connection 230V 50Hz 8 3A power plug Enclosure protection class IP34 Post heating radiator Power 1500 W Preheating radiator Additional heating radiator Fans Supply air Extract air 0 115 kW 0 9 A...

Page 9: ...1 23 30 35 41 44 51 53 56 20 20 20 20 20 21 22 24 26 29 LW dB LWA dB A 58 64 67 71 74 75 78 80 82 84 62 59 61 64 67 69 72 73 75 77 41 50 54 60 64 65 67 70 73 75 39 43 45 50 54 55 57 58 59 62 Sound pre...

Page 10: ...ink between connectors 3 and 5 from the female side of the control panel connector Post heating control PWM level adjustment 4 5 6 Protective earth to a separate block 7 8 9 1 Supply air fan 2 3 Extra...

Page 11: ...nnector GND S GND S MC VENTILATION UNIT Four terminal connector MV VENTILATION UNIT GND AN I RM I RM O E I LED E O PROGRAMMING CONNECTORS OF THE MOTHERBOARD CONTACT DATA GUARD FUNCTION NORMAL SITUATIO...

Page 12: ...RS 485 Common RH optional 946147 Nomak 2x2x0 5 0 5 0 10V LED G G0 Y1 Y2 DI1 A1 Y3 A2 Y4 U1 A B C S DI2 G0 Vallox Procontrol 949034 S LED S B term CONFIG Control signal S Cooker hood or boost switch 11...

Page 13: ...0 11 84 84 35 30 35 7 14 kpl 550 30 25 25 30 Wall mounting plate 283 164 6 604 Bottom edge of the wall mounting plate The top surface of the side panel of the unit can be installed against the finishe...

Page 14: ...ate Installing the ventilation unit to the ceiling mounting plate Remove the unit door Lift the unit and take the wires through the opening in the ceiling mounting plate Lift the ventilation unit agai...

Page 15: ...k water seal Installation height 53 mm installation space 73 mm outer diameter of the duct 12 mm Location of the condensing water outlets R and L models If the Vallox Silent Klick water seal does not...

Page 16: ...8225 6 HR cell 933260 7 Lower support for the HR cell 4102504 8 Upper support for HR cell 3467200 9 Filter frame extraction 978226 10 Filter G4 extract 978227 NO Part Product number 11 Bypass flap ass...

Reviews: