USING THE UNIT

FIREPLACE SWITCH

A switch with timer functions can be connected to the unit. The switch stops the 

extract air fan when the fireplace is being used. NOTE! Starting up the extract 

air fan can reduce the draw of the fireplace! In winter, this can disturb the winter 

mode of the ventilation unit. The situation will return to normal soon after the 

fireplace mode is turned off.

ADJUSTING THE SUPPLY AND EXTRACT AIR 

RATIO 

This function might be needed when the air flows are adjusted at the valves 

during installation. The user does not need to adjust this function once 

the valves have been adjusted, and indeed should not adjust it at all. A 

potentiometer can be used to reduce the supply or extract air flow as required. 
When the potentiometer is set roughly in the centre position, neither the supply 

nor the extract air flow has been reduced. When the potentiometer is turned 

anti-clockwise, the supply air flow is reduced, and when the potentiometer is 

turned clockwise, the extract air flow is reduced.

The potentiometer for adjusting  

the supply and extract air flows

TROUBLESHOOTING

Flashing LED

Problem

Correction

1

NTC sensor of the supply air from the cell is faulty Check the sensor and the wires, replace as required

2

NTC sensor of the extract air is faulty 

Check the sensor and the wires, replace as required

3

NTC sensor of the extract air is faulty 

Check the sensor and the wires, replace as required

4

NTC sensor of the exhaust air is faulty 

Check the sensor and the wires, replace as required

5

NTC sensor of the outdoor air is faulty 

Check the sensor and the wires, replace as required

6

The supply air fan has stopped

Check the wiring of the fan, replace the fan as required

7

The extract air fan has stopped

Check the wiring of the fan, replace the fan as required

8

EEPROM is faulty 

Replace the circuit board

Concealed installation of  

the fireplace switch (optional)

TROUBLESHOOTING TABLE

If the ventilation unit is affected by any of the errors listed in the table, the unit will report the error through the error relay, 

signal light, and circuit board LEDS. The number of flashes indicates the nature of the error.
The error relay can be connected to remote monitoring.  

NOTE! When remote monitoring is used, the signal light of the control panel cannot be turned on.

MAINTENANCE REMINDER

If a signal light is connected to the connectors of the unit’s error relay, the unit will send a reminder of service need every 

six months,. If connected, the signal light will flash every second. Sounds made by the relay can then be heard from 

inside the unit. The maintenance reminder will be set off automatically when the door of the ventilation unit is opened or 

the power is turned off. The maintenance reminder can also be set off manually.

The Vallox Simple Control panel, and the Vallox 

X-Line PTXP MC and PTXPA MC control hoods, 

VAK 0-10 VDC:

•  The low speed is turned on, then higher-lower-higher
  -  Low speed under 4 V
  -  High speed over 6 V
  -  The selected speed will always be turned  

   on for 1-5 seconds

Vallox Delico PTD EC control hood:

•  The damper is closed, then open-closed-open
•  Press at a 1-5 second interval.

The service reminder will only be set off if it has been activated. Refer to the maintenance instructions for the necessary 

maintenance measures.

Summary of Contents for 101 MC R

Page 1: ...Manual MANUAL Ventilation unit Document D4686 Valid from 02 05 2022 Updated 16 05 2022 Model Vallox 101 MC R Vallox 101 MC L Type C3740 ...

Page 2: ...ack of knowledge and experience do not ensure safe operation of the unit Such persons can use the unit under supervision or by following the instructions of someone who is responsible for their safety 12 13 14 Vallox Simple Control panel ordered separately Vallox ProControl panel ordered separately 15 Ceiling bushing for electric wires Vallox Delico PTD EC optional 14 optional 13 optional 12 Vallo...

Page 3: ...at recovery cell is bypassed when the outdoor temperature is above 14 C The heat recovery will be turned on when the outdoor temperature falls below 12 C In the AUTO position the unit will operate as follows around the year The default post heating setting is 17 C The unit will bypass the heat recovery cell when the temperature of the outdoor air exceeds 14 C The heat recovery will be turned on wh...

Page 4: ...f the outdoor air is faulty Check the sensor and the wires replace as required 6 The supply air fan has stopped Check the wiring of the fan replace the fan as required 7 The extract air fan has stopped Check the wiring of the fan replace the fan as required 8 EEPROM is faulty Replace the circuit board Concealed installation of the fireplace switch optional TROUBLESHOOTING TABLE If the ventilation ...

Page 5: ...s on the ambient dust concentration It is recommended that the filters be replaced every spring and autumn or at the very least once a year HEAT RECOVERY CELL Check that the heat recovery cell D is clean roughly once a year when the filters are being replaced Clean by washing as required Remove the sealing strip E above the heat recovery cell in the direction of the arrow Also remove the extract a...

Page 6: ...recovery cell 5 Disconnect the quick connector H of the supply air fan T and or the extract air fan P cables 6 Push the fan cables and the rubber feed through I into the fan chamber 7 Remove the screws used to fasten the fans J 3 screws per fan Undo the mounting screws K 3 screws per fan of the air flow control grille of the fan and remove the grille S 8 Remove the fan from the unit by pulling it ...

Page 7: ...e heating season begins e g during autumn maintenance check that the condensing water outlets in the bottom pool are not clogged To check this pour some water into the pool Clean as required Water must at all times be kept out of the electrical system See the condensing water connections on page 15 291 291 147 5 147 5 R model L model Installation of the Vallox Silent Klick siphon on the bottom poo...

Page 8: ...al resistor 1500 W Pre heating Additional heating Fans Supply air Extract air 0 115 kW 0 95 A EC 0 115 kW 0 95 A EC Specific energy consumption SEC in a cold climate in a temperate climate A A Operating efficiencies Annual efficiency Supply air efficiency Specific Fan Power SFP 75 82 1 33 kW m3 h 63 dm3 s Filters Supply air Extract air ISO Coarse 75 ISO ePM ISO Coarse 75 Heat recovery bypass Autom...

Page 9: ...1 74 78 83 85 88 88 54 57 63 66 70 75 78 79 80 LWA dB A 43 53 57 61 65 68 71 72 74 35 40 45 49 53 55 58 59 60 Sound pressure level coming through the envelope of the unit in the room in which it is installed 10m sound absorption Adjustment position Air flows supply extract Adjustment position V 3 1 4 1 5 2 6 2 7 3 8 1 9 2 10 2 11 4 Air flow dm s 15 20 24 30 33 40 42 48 52 58 61 68 70 76 78 84 83 8...

Page 10: ...link between connectors 3 and 5 from the female side of the control panel connector Post heating control PWM level adjustment 4 5 6 Protective earth to a separate block 7 8 9 1 Supply air fan 2 3 Extract air fan 4 5 LINE NEUTRAL SLI SNI SLO SNO SFL Extract air NTC Outdoor air NTC Supply air to the apartment NTC Exhaust air NTC Supply air from the cell NTC SFN EFL EFN FSO FSI AHL AHN PHL PHN 230V 5...

Page 11: ...ector GND S GND S MC VENTILATION UNIT Four terminal connector MV VENTILATION UNIT GND AN I RM I RM O E I LED E O PROGRAMMING CONNECTORS OF THE MOTHERBOARD CONTACT DATA GUARD FUNCTION NORMAL SITUATION OPEN ACTIVATED CLOSED HOUSE AUTOMATION NORMAL SITUATION OPEN ERROR SITUATION HOOD OR VENTILATION UNIT CLOSED ACTIVATED GUARD FUNCTION FLASHING POSITION OF THE DAMPER DAMPER CLOSED CONTACT OPEN DAMPER ...

Page 12: ...485 Common RH optional 946147 Nomak 2x2x0 5 0 5 0 10V LED G G0 Y1 Y2 DI1 A1 Y3 A2 Y4 U1 A B C S DI2 G0 Vallox Procontrol 949034 S LED S B term CONFIG Control signal S Cooker hood or boost switch 11 2 VDC GND DISTRIBUTION BOARD L N 24V Error relay LED Nomak 2x2x0 5 0 5 Modbus RS 485 Nomak 2x2x0 5 0 5 Cable types specified in the drawing are indicative 2x0 5 2x0 5 Internal connection of the ventilat...

Page 13: ...ll mounting plate The top surface of the side panel of the unit can be installed against the finished ceiling surface When the wall mounting plate is used it must be observed that the ventilation unit will rise roughly 10mm above the final installation height The outer diameter of the duct is 12mm Mounting on the wall NOTE Avoid mounting the unit on a hollow echoing partition wall or on a bedroom ...

Page 14: ...ing plate Installing the ventilation unit to the ceiling mounting plate Remove the unit door Lift the unit and take the wires through the opening in the ceiling mounting plate Lift the ventilation unit against the ceiling mounting plate so that it locks in place The unit has become locked on the ceiling mounting plate when the two operating levers on the mounting plate have been restored to the sa...

Page 15: ... siphon Installation height 53 mm installation space 73 mm outer diameter of the duct 12 mm Location of the condensing water outlets R and L models If the Vallox Silent Klick siphon does not fit into the unit directly the elbow can be installed at the bottom and the siphon can be installed on the wall This installation method requires that there is a 47 mm space underneath the unit The elbow requi...

Page 16: ...4102504 8 Upper support for HR cell 3467200 9 Filter frame extraction 978226 10 Coarse filter for extract air 978227 NO Part Product number 11 HR cell bypass damper assembly 4102523 12 Damper motor 930621 13 Post heating resistor 942220 14 Door 4102334 15 Mounting screw of the door 990712 16 Motherboard 949035 17 Safety switch 948370 18 Glass tube fuse 320 mA slow 5x20 mm 952486 19 NTC sensor spec...

Reviews: