VALLOX 252 M

13

Heat Recovery Defrosting

The TS5 temperature thermostat directs the operation of the preheater
(LP1) on the basis of the measurement data supplied by the temperature
sensor, preventing the risk of freezing and the stopping of the supply air
fan (TF). If the capacity of the preheater (LP1) is not sufficient, or if there is
no preheater, the TS1 defrosting thermostat of the heat recovery cells
stops the TF supply air fan on the basis of the measuring data on the
temperature sensor, thereby preventing the heat recovery cell from free-
zing. As soon as the risk of frosting passes, the fan restarts automatically.
The threshold temperature for defrosting (-2…+6 ˚C) and the difference
area (2 ˚C) can be set on the thermostat.

Overheating Protection of the Heating Unit

Overheat protection thermostats TZ1 and TZ2 monitor the surface tempe-
rature in the LP1 heating unit. If surface temperature exceeds the
threshold, overheat protection is triggered and power supply to the hea-
ting unit is stopped. The TZ1 overheating protector is reset automatically,
and the TZ2 protector manually.

Damper Motors of the Outdoor and/or Extract Air Ducts

The spring return damper motors (24VAC) that may be installed outside
the ventilation unit, in the outdoor or extract air ducts, can be controlled
with control voltage (24 VAC) coming from the ventilation unit: when the
ventilation unit is stopped, also the control voltage fed from the unit is
stopped.

Alarms

The PDS1 and PDS2 pressure difference switches monitor the pressure
difference on the supply and discharge air sides. If the pressure differen-
ce grows too large because of dirty filters or clogged ducts, remote moni-
toring receives potential free operation mode information from the unit.

Control of Operation

If needed, the ventilation unit can be stopped by controlling the contac-
tors in the unit (Min., 1/2, Max.) or by controlling power supply via the
contactor in the distribution panel.

Fan Speed Adjustment

The ventilation unit can feed control voltage (24VAC) to the remote moni-
toring center, and the remote monitoring center can then direct the fan
capacity of the ventilation unit in three steps according to the control
signal (24VAC) received by the Min., 1/2, and Max. contacts in the
connection box. Remote monitoring receives potential free operation mo-
de information on the mode selected (Min., 1/2, Max.).

Supply Air Temperature

A regulating valve (not included in the VALLOX 252 delivery) directs the
operation of the LP2 post-heating unit on the basis of the measurement
data given by the thermostat sensor in the supply air duct. The aiming is
to keep supply air temperature at the temperature value set with the regu-
lating valve (10…25 ˚C).

Heat Recovery Bypass

With the help of control voltage (24VAC) fed from the ventilation unit to
the remote monitoring center and its control functions, the heat recovery
bypass function can be directed according to the control signal (24 VAC)
received by the NC contact in the connection box. When heat recovery
bypass is activated, the preheater (LP1), if used, and the post-heating unit
(LP2) are deactivated.

DESCRIPTION OF OPERATION VALLOX 252 M VKL REMOTE MONITORING CONTROL UNIT

Parts List

FG

Damper motor

Automatic heat recovery bypass 24V, 2W, 8Nm

Standard

X

IU

LP1

Preheater

Electric radiator 2.5kW

Options

IU

LP2

Post-heating unit

Water radiator 5kW, 70/50oC

Options

IU

LTO1

Heat recovery cells

2-step,   = 70 %

Standard

X

IU

LTO2
PDS1

Pressure difference switch

Adjustment range 0...500Pa (420)

Options

IU

Pressure guard for supply air

PDS2

Pressure difference switch
Pressure guard for discharge air

Adjustment range 0...500Pa (420)

Options

IU

PF

Discharge air fan

qv = 230 dm

3

/s (100Pa)

Standard

X

IU

SU

Filter

Supply air EU7, discharge air EU5

Standard

X

IU

SV

Regulating valve

Self-operating radiator thermostat

Not included in the
ventilation unit delivery

TS1

Temperature thermostat

Discharge air temperature

Heat recovery defrosting 

Adjustment range -2...6 ˚C (2)

Standard

X

IU

TS5

Temperature thermostat

Discharge air temperature

Preheating, electric

Adjustment range -0...8 ˚C (2)

Standard

X

IU

TF

Supply air fan

qv = 210 dm

3

/s (100Pa)

Standard

X

IU

TZ1

Overheat protector of the electric radiator

Automatic reset (+60 ˚C)

Included in LP1 / LP2

IU

TZ2

Overheat protector of the electric radiator

Manual reset (+95 ˚C)

Included in LP1 / LP2

IU

FGU

Damper motor

Damper motor in the outdoor air duct
(spring return) 24VAC

IU

FGJ

Damper motor

Damper motor in the extract air duct
(spring return) 24VAC

IU

Code

Name

Technical details 

Equip-

Delivery

(factory settings in parentheses)

Note!

ment

Responsibility

Summary of Contents for 252 M

Page 1: ...charge air 210 dm3 s 100 Pa 230 dm3 s 100 Pa 2 heat recovery cells 70 Manual or remote monitoring control 2 5 kW 11 A 2 5 kW 11 A Approx 5kW EU 3 EU 7 EU 3 EU 5 210 kg 2x230 W 1 A 2x230 W 1 A Fans Hea...

Page 2: ...tarts when outdoor air temperature falls below ca 5 C VALLOX 252 M can be operated with the manual cont rol unit contained in the delivery With the manual control unit you can select the min or max ve...

Page 3: ...8 Fan speeds 90 100 110 130 140 160 200 230 Control voltage V 200 230 275 350 390 450 590 675 Input power W 3 1 2 3 4 5 6 7 8 90 100 110 130 140 160 200 230 200 230 275 350 390 450 590 675 74 85 99 1...

Page 4: ...OW Sound power level from VALLOX to discharge air ducts by octave band Lw dB CONTROL POSITION AIR FLOW Medium frequency of the octave band Hz Sound power level coming from VALLOX through the envelope...

Page 5: ...ntering the radiator tv 55 C Temperature of air entering the radiator ti 15 C Cooling of water in the radiator C Water flow dm3 s Total output of the radiator kW Cooling of water in the radiator C Wat...

Page 6: ...OL 2 6 Control Diagram VALLOX 252 M MANUAL CONTROL UNIT Distribution Panel 2x16A if equipped with a preheater Internal electrical and control connections Post heating unit electric Preheater electric...

Page 7: ...entilation zone Supply Air Temperature The control adjustment center of the unit directs the operation of the post heating unit LP2 on the basis of the measuring data on the sensor of the TS2 temperat...

Page 8: ...L CONTROL UNIT 2 8 Control Diagram VALLOX 252 M VKL MANUAL CONTROL UNIT Distribution Internal electrical and control connections Post heating unit water circulation Preheater electric Sound attenuator...

Page 9: ...ir Temperature A regulating valve not included in the VALLOX 252 M delivery directs the operation of the LP2 post heating unit on the basis of the measurement data given by the thermostat sensor in th...

Page 10: ...CONTROL Distribution Panel Internal electrical and control connections Post heating unit electric Preheater electric VENTILATION ZONE 2x16A if equipped with a preheater Pressure unit Pressure unit Sou...

Page 11: ...ccording to the control signal 24VAC received by the Min 1 2 and Max contacts in the connection box Remote monitoring receives potential free operation mo de information on the mode selected Min 1 2 M...

Page 12: ...L MANUAL CONTROL UNIT Distribution Panel Internal electrical and control connections Post heating unit water Preheating electric Ventilation zone Pressure switch REMOTE MONITORING CONTROL CENTER OF TH...

Page 13: ...l 24VAC received by the Min 1 2 and Max contacts in the connection box Remote monitoring receives potential free operation mo de information on the mode selected Min 1 2 Max Supply Air Temperature A r...

Page 14: ...he unit is equipped with an adjustable socle If the unit is mounted on a wall keep in mind the weight of the unit 190kg and vibration damping The unit is splash proof IP34 so it can also be mounted in...

Page 15: ...enuator unit also features detachable attenuation segments in supply and discharge air ducts 4 250 external fittings enable the laying of ducts straight from the unit by using bends etc The top of the...

Page 16: ...to be connected through the lead through tubes to the connection box inside VALLOX 252 If a water heating unit is used lead the supply and return pipes not included in the delivery of the heating uni...

Page 17: ...ith remote monitoring control Selection of Control Voltages for Capacity Modes Min 1 2 and Max BEFORE SELECTING CONTROL VOLTAGES MAKE SURE THAT THE UNIT HAS BEEN DISCONNECTED FROM THE MAINS SUPPLY If...

Page 18: ...al reset PDS1 Supply air duct pressure difference switch optional PDS2 Discharge air duct pressure difference switch optional F1 Fuse 4A F2 Fuse 1 6A TF Supply air fan 2x230W PF Discharge air fan 2x23...

Page 19: ...with a PREHEATER and a POST HEATING UNIT WITH WATER CIRCULATION the L1 and L on the terminal block are connected In this case THE PREHEATER DOES NOT NEED a separate power supply NOTE When the VALLOX...

Page 20: ...n on the 1 2 mode Operation mode information on the Max mode Operation mode information from the pressure difference switch Operation mode information from Pos 1 discharge air duct Entering operation...

Reviews: