VALLOX 252 M

MOUNTING INSTRUCTIONS FOR THE SOUND ATTENUATOR

2

16

Mounting

NOTE! BEFORE MOUNTING, CHECK THE MODEL OF VALLOX 252 M (L or R).

• Detach the door of the sound attenuator. (See the adjoining picture.)

• Detach the sleeves equipped with draught limiters (see the figure, item D).

• Cut through the lead-in sealings for the cable sleeves at the bottom of the extract duct

of the sound attenuator unit (no isolation inside). NOTE! VALLOX 252 model L or R.
(See the figure.)

• If VALLOX 252 is equipped with a water heating unit, also detach the sound

attenuation segment located in the supply air duct of the unit. NOTE! VALLOX 252
model L or R. (See the figure.)

• Lift the sound attenuator unit on top of VALLOX 252. Make sure that the cable sleeves

go through. (See the figure, item D.)

• Mount the lead-through cable tubes (included in the delivery), pushing them through

the lead-in sealings on top of the sound attenuator unit, and screwing them to the
cable sleeves. (See the figure, item C.)

• Lay the cables to be connected through the lead-through tubes to the connection box

inside VALLOX 252.

• If a water heating unit is used, lead the supply and return pipes (not included in the

delivery) of the heating unit through the lead-in sealings on top of the sound attenuator
unit and VALLOX 252, and connect them to the supply and return water outlets with a
straight fitting, for instance.
(See the figure, items A and B.)

• Mount the sound attenuation segment in place.

• Carefully fix the door of the sound attenuator in place.

• Fix the ducts steadily and tightly to the outlets. If ducts are to be isolated, do so

following the ventilation plan.

Supply and return water

 pipe Ø15/13 2 pcs

Straight fitting

MS15 2 pcs

Supply and return

water outlet 2 pcs

Lead-through tubes

for cables 3 pcs

Sleeve equipped with draught-limiter 3 pcs

Cable sleeve 3 pcs

Supply and return

water pipe Ø15/13 2 pcs

Lead-in sealings for supply

and return water pipes 2 pcs

Sound attenuator unit

(Note! Vallox model)

Duct fitting

Ø250 4 pcs

Lead-through tubes for cables 3 pcs

Lead-in sealing for cable

lead-through tube 3 pcs

Lead-in sealing for cable

sleeve 3 pcs (bottom)

VALLOX 250 L

(Note! model)

Sound attenuation

segment

Summary of Contents for 252 M

Page 1: ...charge air 210 dm3 s 100 Pa 230 dm3 s 100 Pa 2 heat recovery cells 70 Manual or remote monitoring control 2 5 kW 11 A 2 5 kW 11 A Approx 5kW EU 3 EU 7 EU 3 EU 5 210 kg 2x230 W 1 A 2x230 W 1 A Fans Hea...

Page 2: ...tarts when outdoor air temperature falls below ca 5 C VALLOX 252 M can be operated with the manual cont rol unit contained in the delivery With the manual control unit you can select the min or max ve...

Page 3: ...8 Fan speeds 90 100 110 130 140 160 200 230 Control voltage V 200 230 275 350 390 450 590 675 Input power W 3 1 2 3 4 5 6 7 8 90 100 110 130 140 160 200 230 200 230 275 350 390 450 590 675 74 85 99 1...

Page 4: ...OW Sound power level from VALLOX to discharge air ducts by octave band Lw dB CONTROL POSITION AIR FLOW Medium frequency of the octave band Hz Sound power level coming from VALLOX through the envelope...

Page 5: ...ntering the radiator tv 55 C Temperature of air entering the radiator ti 15 C Cooling of water in the radiator C Water flow dm3 s Total output of the radiator kW Cooling of water in the radiator C Wat...

Page 6: ...OL 2 6 Control Diagram VALLOX 252 M MANUAL CONTROL UNIT Distribution Panel 2x16A if equipped with a preheater Internal electrical and control connections Post heating unit electric Preheater electric...

Page 7: ...entilation zone Supply Air Temperature The control adjustment center of the unit directs the operation of the post heating unit LP2 on the basis of the measuring data on the sensor of the TS2 temperat...

Page 8: ...L CONTROL UNIT 2 8 Control Diagram VALLOX 252 M VKL MANUAL CONTROL UNIT Distribution Internal electrical and control connections Post heating unit water circulation Preheater electric Sound attenuator...

Page 9: ...ir Temperature A regulating valve not included in the VALLOX 252 M delivery directs the operation of the LP2 post heating unit on the basis of the measurement data given by the thermostat sensor in th...

Page 10: ...CONTROL Distribution Panel Internal electrical and control connections Post heating unit electric Preheater electric VENTILATION ZONE 2x16A if equipped with a preheater Pressure unit Pressure unit Sou...

Page 11: ...ccording to the control signal 24VAC received by the Min 1 2 and Max contacts in the connection box Remote monitoring receives potential free operation mo de information on the mode selected Min 1 2 M...

Page 12: ...L MANUAL CONTROL UNIT Distribution Panel Internal electrical and control connections Post heating unit water Preheating electric Ventilation zone Pressure switch REMOTE MONITORING CONTROL CENTER OF TH...

Page 13: ...l 24VAC received by the Min 1 2 and Max contacts in the connection box Remote monitoring receives potential free operation mo de information on the mode selected Min 1 2 Max Supply Air Temperature A r...

Page 14: ...he unit is equipped with an adjustable socle If the unit is mounted on a wall keep in mind the weight of the unit 190kg and vibration damping The unit is splash proof IP34 so it can also be mounted in...

Page 15: ...enuator unit also features detachable attenuation segments in supply and discharge air ducts 4 250 external fittings enable the laying of ducts straight from the unit by using bends etc The top of the...

Page 16: ...to be connected through the lead through tubes to the connection box inside VALLOX 252 If a water heating unit is used lead the supply and return pipes not included in the delivery of the heating uni...

Page 17: ...ith remote monitoring control Selection of Control Voltages for Capacity Modes Min 1 2 and Max BEFORE SELECTING CONTROL VOLTAGES MAKE SURE THAT THE UNIT HAS BEEN DISCONNECTED FROM THE MAINS SUPPLY If...

Page 18: ...al reset PDS1 Supply air duct pressure difference switch optional PDS2 Discharge air duct pressure difference switch optional F1 Fuse 4A F2 Fuse 1 6A TF Supply air fan 2x230W PF Discharge air fan 2x23...

Page 19: ...with a PREHEATER and a POST HEATING UNIT WITH WATER CIRCULATION the L1 and L on the terminal block are connected In this case THE PREHEATER DOES NOT NEED a separate power supply NOTE When the VALLOX...

Page 20: ...n on the 1 2 mode Operation mode information on the Max mode Operation mode information from the pressure difference switch Operation mode information from Pos 1 discharge air duct Entering operation...