VALLOX 252 M
EXTERNAL ELECTRICAL CONNECTIONS VALLOX 252 M - MANUAL CONTROL
19
MANUAL CONTROL UNIT
CAM SWITCH
WINTER
SUMMER
DAMPER MOTOR 24V
AC
FOR OUTDOOR OR
EXTRACT AIR DUCT
5x0.5
ÖPVC-OZ OR SIMILAR
NOTE! When the V
ALLOX 252 M unit is equipped with a
PREHEA
TER and a POST
-HEA
TING UNIT WITH W
ATER
CIRCULA
TION, the L1 and L on the terminal block are
connected. .
In this case, THE PREHEA
TER DOES NOT NEED a separate
power supply
.
NOTE! When the V
ALLOX 252 M unit is equipped with a PREHEA
TER and an ELECTRIC
POST
-HEA
TING UNIT
, a separate 16A power supply is needed for THE PREHEA
TER.
DISTRIBUTION P
ANEL
POS. 2
STATUS
POS. 1
MAX.
1/2
MIN.
STATUS
NC
24VAC
MAX.
1/2
MIN.
N / 24VAC
L10
L1
L
N
-
VALLOX 252 M