background image

"Bus fault" message is
displayed and the unit ope-
rates at speed 1 (check the
fan speed).

• Wiring fault in the carbon dioxide sensor,

in the control panel or in the humidity
sensor.

9

• Contact a maintenance company. The connections have

to be checked and corrected if necessary.

"Freezing alert" message is
displayed and the unit is
stopped.

• Anti-frost of the water-circulating radiator is

active.

NOTE! If there is no non-freezing solution in the
water of the radiator, the radiator is at risk of
freezing.

10

• Immediately troubleshoot the situation. Consult a

maintenance company to find out if there is any non-
freezing solution in the radiator. Check if the circulation
pump is broken, the boiler out of operation etc. The
situation may pass by itself as soon as supply air
temperature exceeds 10 degrees, but do not wait till it
happens.

The desired automatic
adjustment does not stay
on.

• There is a fault in the humidity or carbon

dioxide sensor, one of the sensors is
broken or missing.

11

• Contact a maintenance company. The sensor installation

and connections have to be checked. (The sensors are
optional.)

The unit does not work,
the fans are not running
and no indicator light is lit
in the control panel.

• The door switch may be broken, or the

door is possibly not quite closed.

• The unit is out of power, e.g. because a

fuse has blown.

• The glass tube fuse (located in the control

card behind a protecting plate) the
electronics inside the unit may have blown.

12

• Check the door switch and fuses. The unit includes a

T800 mA glass tube fuse.

• If needed, contact a maintenance company (e.g. to

check the glass tube fuse).

The unit does not obey the
control panel.

13

• Remove or switch off the power supply fuse of the unit,

located in the distribution panel, or the circuit breaker.
Wait for 30 seconds and put the fuse back, or switch the
circuit breaker on. If this does not help, contact a
maintenance company.

"Carbon dioxide alarm"
message is displayed and
the unit is stopped.

• Carbon dioxide alarm. Carbon dioxide

content has exceeded 5000 PPM for more
than two minutes. May be caused by a
fire.

14

• If there is a fire, take the necessary steps.

• You can put the unit in working order by disconnecting the

plug from the wall socket, waiting for 30 seconds and
connecting the plug again.

• Check the cleanliness of the filters and the unit. If needed,

clean or replace the filters.

15

© VALLOX • We reserve the right to make changes without prior notification.

1.09.372E/19.8.2008/PDF

VALLOX 280 SE

Vallox Oy FIN-32200 Loimaa Finland Tel358 2 7636 300 Fax +358 2 7631 539

Internet: www.vallox.com.

FAULT SITUATIONS

After a power failure, the unit starts at minimum fan speed.
All the other selected adjustments and setpoints remain in the memory of the unit.

The filter guard symbol
( ) is displayed and the
unit operates otherwise
normally.

• Pressure in the filter guard (pressure

difference switch) has exceeded the
setpoint.

SYMPTOM

REASON

DO THIS

Summary of Contents for 280 SE

Page 1: ...ake changes without prior notification 1 09 372E 19 8 2008 Code 3487 VALLOX INSTRUCTIONS FOR USE AND MAINTENANCE DIGIT SED ELECTRONIC CONTROLLER WITH LCD DISPLAY Electronically controlled supply extra...

Page 2: ...ascade control p 5 1 12 Heat recovery bypass function p 5 1 13 Anti frost function of heat recovery cell p 6 1 14 Anti frost function in a water circulated post heating unit p 6 1 15 Maintenance remin...

Page 3: ...nit 6 C 15 C exhaust air Changing the setpoints There may be three control panels at most When more than one control panel is used the unit can be adjusted at all the control panels VALLOX We reserve...

Page 4: ...od indoor air is approximately 45 When this control is on the control panel may be used to raise fan speed to the set maximum fan speed and to decrease it to the basic fan speed In humidity control fa...

Page 5: ...The temperature of air blown to the ventilation zone is controlled on the basis of extract air The program tries to keep supply air temperature at a value determined by the difference between extract...

Page 6: ...reezing The automatic function stops the supply and extract air fans as soon as outdoor air temperature falls below 0 C and supply air temperature below 7 C in which case also the control valve become...

Page 7: ...es for 45 minutes During the function the fireplace booster switch symbol is visible in the main display of the control panel The function is selected at the control panel see Section 2 2 1 NOTE The s...

Page 8: ...1 items 5 and 6 in the figure To settings menu See manual RH1 35 RH2 40 CO2 0821 PPM Out 20 In 20 Sup 20 Exh 20 Temp setting 20C 5 Scrolling up With this button you can scroll the displays upward 6 S...

Page 9: ...actory settings see manual The adjustment interval for humidity and carbon dioxide adjustments is selected with the and buttons The adjustment interval refers to minutes 2 3 9 Adjustment interval Adju...

Page 10: ...40 The desired cell bypass temperature is selected with the and buttons If outdoor temperature is lower than cell bypass temperature the summer winter damper is in the winter position 2 3 15 Changing...

Page 11: ...d Exit and pressing or Changes in fan speed Sp and supply air temperature Tmp are only made for the hours desired in other cases use N no change to previous Monday D 1 07 00 hours H 7 fan speed 2 Sp 2...

Page 12: ...ezing protection cell 3 C Freezing protection hysteresis 3 C Preheating setting 5 C Maintenance reminder 4 months Cell bypass 12 C Cascade control not used Humidity level RH level adjustment automatic...

Page 13: ...filter can be cleaned with 25 C 30 C water and washing up liquid It must not be washed or dried roughly but by pressing gently When washing is done properly filters stand cleaning 4 to 5 times F5 and...

Page 14: ...ater connections remove the socle If a condensing water tank is in use it can be drawn out by pulling it forward The tank can be removed for emptying and cleaning When the condensing water outlet is i...

Page 15: ...using the control panel Section 2 3 22 If the preheating radiator does not operate check if over heating protection prevents it from operating press the overheating protection reset button and measure...

Page 16: ...the control card behind a protecting plate the electronics inside the unit may have blown 12 Check the door switch and fuses The unit includes a T800 mA glass tube fuse If needed contact a maintenanc...

Reviews: