1.5. Ventilation control with carbon dioxide sensor (option)

• In carbon dioxide control, VALLOX 280 SE adjusts fan speed so as to keep carbon

dioxide content in the ventilation zone below the setpoint. When two or more sensors
are used, fan speed is adjusted according to the highest measuring result.

• 1 to 5 carbon dioxide sensors can be connected as options to the VALLOX 280 SE unit.
• The adjustment is switched on / off and, if needed, the setpoint (500…2000 ppm) is set

at the control panel. The factory setting is 900 ppm. The recommended maximum car-
bon dioxide content in good indoor air is 1,000 ppm.

• When carbon dioxide control is on, the control panel may be used to raise fan speed to

the maximum fan speed and to decrease it to the basic fan speed. In carbon dioxide
control, maximum fan speed limitation is enabled.

1.6. Ventilation control with humidity sensor (option)

There are two methods for adjusting fan speed.
1.

Automatic humidity setting

, which is suitable for controlling humidity in washing rooms, for

instance. The program records current humidity level and selects it as the setpoint, which
it then uses as the target for drying air in a bathroom after a shower, for example. The
setpoint automatically varies according to season, for instance, and is always at the right
level. This setting is factory selected.

2. Humidity level can also be set 

fixed

. The setting can range within the range of

1...99 %RH and is set at the control panel. This can be used in public saunas and
swimming pools, for instance. The program aims at keeping humidity at the setpoint.
The setpoint can be changed if needed.

The mode of adjusting is chosen at the controller. Recommended humidity content of good
indoor air is approximately 45%.
• When this control is on, the control panel may be used to raise fan speed to the set

maximum fan speed and to decrease it to the basic fan speed.

• In humidity control, fan speed varies between the basic and maximum fan speeds se-

lected.

• When the unit is first taken into use with 

automatic setpoint search enabled

 (factory setting),

it takes 3 to 10 hours for the program to define the value

. During this time, humidity adjustment is

not enabled (because the first value, selected at the factory, is 100%).

• Automatic search is enabled even if humidity control is not selected.

1.7. Ventilation control with voltage or current signal

• VALLOX 280 SE fan power can be controlled with a voltage or current signal coming

from remote monitoring.

• The signal can be used to select speeds 0–8. However, the set maximum fan speed

cannot be exceeded if carbon dioxide or humidity adjustment is active, or if maximum
fan speed limitation has been selected at the settings menu to be in operation all the time
(see the instructions for using the control panel, Section 2.3.6.).

• The signal changes the basic fan speed.
• The signal does not lock fan speed, i.e. fan speed can be changed at the control panel

within the set limits. Carbon dioxide and humidity adjustment also operate within the set
limits.

1.8. Ventilation control with remote monitoring system (option)

• With an optional LON converter, VALLOX 280 SE can be connected to an remote moni-

toring system.

• When VALLOX 280 SE is connected to the remote monitoring system, compatibility bet-

ween the two needs to be ensured.

• The remote monitoring system can control the same functions as the control panel does.
• The remote monitoring system works in parallel with the control panel as well as carbon

dioxide and humidity sensors.

Carbon dioxide sensor (CO

2

)

Humidity sensor (%RH)

1.5.

LON converter

1.6.

© VALLOX • We reserve the right to make changes without prior notification.

Summary of Contents for 280 SE

Page 1: ...ake changes without prior notification 1 09 372E 19 8 2008 Code 3487 VALLOX INSTRUCTIONS FOR USE AND MAINTENANCE DIGIT SED ELECTRONIC CONTROLLER WITH LCD DISPLAY Electronically controlled supply extra...

Page 2: ...ascade control p 5 1 12 Heat recovery bypass function p 5 1 13 Anti frost function of heat recovery cell p 6 1 14 Anti frost function in a water circulated post heating unit p 6 1 15 Maintenance remin...

Page 3: ...nit 6 C 15 C exhaust air Changing the setpoints There may be three control panels at most When more than one control panel is used the unit can be adjusted at all the control panels VALLOX We reserve...

Page 4: ...od indoor air is approximately 45 When this control is on the control panel may be used to raise fan speed to the set maximum fan speed and to decrease it to the basic fan speed In humidity control fa...

Page 5: ...The temperature of air blown to the ventilation zone is controlled on the basis of extract air The program tries to keep supply air temperature at a value determined by the difference between extract...

Page 6: ...reezing The automatic function stops the supply and extract air fans as soon as outdoor air temperature falls below 0 C and supply air temperature below 7 C in which case also the control valve become...

Page 7: ...es for 45 minutes During the function the fireplace booster switch symbol is visible in the main display of the control panel The function is selected at the control panel see Section 2 2 1 NOTE The s...

Page 8: ...1 items 5 and 6 in the figure To settings menu See manual RH1 35 RH2 40 CO2 0821 PPM Out 20 In 20 Sup 20 Exh 20 Temp setting 20C 5 Scrolling up With this button you can scroll the displays upward 6 S...

Page 9: ...actory settings see manual The adjustment interval for humidity and carbon dioxide adjustments is selected with the and buttons The adjustment interval refers to minutes 2 3 9 Adjustment interval Adju...

Page 10: ...40 The desired cell bypass temperature is selected with the and buttons If outdoor temperature is lower than cell bypass temperature the summer winter damper is in the winter position 2 3 15 Changing...

Page 11: ...d Exit and pressing or Changes in fan speed Sp and supply air temperature Tmp are only made for the hours desired in other cases use N no change to previous Monday D 1 07 00 hours H 7 fan speed 2 Sp 2...

Page 12: ...ezing protection cell 3 C Freezing protection hysteresis 3 C Preheating setting 5 C Maintenance reminder 4 months Cell bypass 12 C Cascade control not used Humidity level RH level adjustment automatic...

Page 13: ...filter can be cleaned with 25 C 30 C water and washing up liquid It must not be washed or dried roughly but by pressing gently When washing is done properly filters stand cleaning 4 to 5 times F5 and...

Page 14: ...ater connections remove the socle If a condensing water tank is in use it can be drawn out by pulling it forward The tank can be removed for emptying and cleaning When the condensing water outlet is i...

Page 15: ...using the control panel Section 2 3 22 If the preheating radiator does not operate check if over heating protection prevents it from operating press the overheating protection reset button and measure...

Page 16: ...the control card behind a protecting plate the electronics inside the unit may have blown 12 Check the door switch and fuses The unit includes a T800 mA glass tube fuse If needed contact a maintenanc...

Reviews: