SCOPE OF APPLICATION - INTENDED USE
Vallox Exxeo roof fans are intended as fans for extract air ventilation
systems. The maximum temperature of air extracted by the roof fans is
+40°C. The structure of Vallox Exxeo roof fans is designed so that water is
led out without ending up in the duct system.
Vallox Exxeo roof fans may be mounted on top of a Vallox Exxeo roof
penetration part or a penetration made on site. When required, the
mounting frame included in the standard delivery can be used.
Vallox Exxeo roof fans come in seven different sizes 150...4100 (0.15...4.1
m³/s, ps= 150 Pa)
Three different models are available for each size:
• Basic model, equipped with a control panel
- model marking, e.g. Vallox Exxeo 4100 (air volume 4,100 dm³/s, ps =
150 Pa)
• DPC model, equipped with a control panel + pressure control
- model marking, e.g. Vallox Exxeo 4100 DPC (air volume 4,100 dm³/s,
ps = 150 Pa)
• DS model, equipped with a dual speed converter. The model can
replace a 2-speed 3-phase AC roof fan. The control requires an existing
cable with 7 poles (2x3-phase PE).
- model marking, e.g. Vallox Exxeo 4100 DS (air volume 4,100 dm³/s,
ps = 150 Pa)
NOTE
If the roof fan is used
as an extract fan for
a kitchen/grease
duct, grease removal
prior to the fan must
be ensured as well
as not exceeding
the maximum
temperature of
extract air.
TECHNICAL DATA
• Upward-blowing
• Plastic fan wheel with EC motor
• Controls integrated into the frame
• Enclosure soundproofed on the inside
• Roof fan’s metal parts meet the C4 requirements (EN ISO 12944-2)
• Enclosure protection class of electrical equipment IP54
• All models come with a connected safety switch
- Basic and DPC models: Katko KSM 416 U (100x128x56)
- DS model: Katko TKM 616 U (97x131x106)
• Multiple control options (see the technical specifications table)
• All models are equipped with air flow measuring tubes
• All models are tiltable, and the structure is easy to open for
maintenance
• The enclosure is made of magnesium-zinc coated sheet metal Can be
painted to order with RAL tones
• CE marking
INTRODUCTION
NOTE
Before setup, the
roof fan instruction
manual must be
read thoroughly. The
installation must be
made according to
the instructions, and
all of the necessary
safety equipment
must be installed.