background image

Low-energy ventilation unit 

with heat recovery

© Vallox
1.09.609 E
Valid from 

11.4.2014

1   Supply air fan
2   Extract air fan
3   Antifreeze thermostat 
4   Preheating radiator

 

900 W (TSK Multi 50 SC BP)

   1500 W (TSK Multi 80 SC BP)
5   Heat recovery cell
6   Outdoor air fi lter F7
7   Outdoor air fi lter G4
8   Extract air fi lter G4
9   Summer/winter damper
10  Safety switch
11  Extract air potentiometer 

 

(in the connection box)

12  Speed selector switch (1-4) 

 (option)

12

Code 

TSK MULTI 50 SC BP 3605-1, 3605-2

TSK MULTI 80 SC BP 3604-1, 3604-2

Operating, maintenance and technical instructions

VALLOX TSK MULTI 50 SC BP

VALLOX TSK MULTI 80 SC BP

Electrical connection

230 V, 50 Hz, = 4.5 A

230 V, 50 Hz, = 8.8 A

Degree of protection provided 
by enclosures

IP 34

IP 34

Integrated direct-current fan
 

Extract air

0.043 kW 0.32 A 62 dm

3

/s 50 Pa

0.071 kW 0.5 A 93 dm

3

/s 100 Pa

 

Supply air

0.043 kW 0.32 A 54 dm

3

/s 50 Pa

0.071 kW 0.5 A 77 dm

3

/s 100 Pa

Heat recovery 

Cross-counter fl ow cell, 

 > 80%

Cross-counter fl ow cell, 

 > 80%

Heat recovery bypass

Motorised damper

Motorised damper

Electric preheating unit

900 W, 3.9 A

max 1500 W, 6.5 A

Filters
 

Supply air

G4 + F7

G4 + F7

 

Extract air

G4

G4

Weight

45.0 kg

58.5 kg

Ventilation power adjustment

SC controller, 0-10 VDC

SC controller, 0-10 VDC

Remote monitoring control 0-10 VDC

Remote monitoring control 0-10 VDC

Options

SC controller

SC controller

SlimLine PTXP MC cooker hood

SlimLine PTXP MC cooker hood

SlimLine PTXPA MC cooker hood

SlimLine PTXPA MC cooker hood

TECHNICAL DATA

SC BP

Vallox TSK

Multi 

50

80

1

10

9

8

7

5

6

3

4

2

11

Summary of Contents for TSK MULTI 50 SC BP

Page 1: ...provided by enclosures IP 34 IP 34 Integrated direct current fan Extract air 0 043 kW 0 32 A 62 dm3 s 50 Pa 0 071 kW 0 5 A 93 dm3 s 100 Pa Supply air 0 043 kW 0 32 A 54 dm3 s 50 Pa 0 071 kW 0 5 A 77 d...

Page 2: ...air ow Extract air flow can be reduced at the potentiometer located in the electrical box This feature can be useful when the ventilation system is adjusted In other situations the potentiometer and...

Page 3: ...sects heavy pollen and other dust An F7 class fine filter B filters off fine dust invisible to the eye Extract air is filtered with a coarse filter C By using original Vallox filters you ensure good o...

Page 4: ...ach other by pressing the white tongue 4 Detach the connector of the preheating radiator If there is no preheating radiator in the unit move to item 6 2 Pull the bypass duct filter stand bundle out an...

Page 5: ...r needs to flow out from the ventilation unit without hindrance In carrying out maintenance for instance in autumn before the beginning of the heating season make sure that the condensing water outlet...

Page 6: ...9 40 7 42 3 51 0 50 0 47 6 45 5 43 4 38 2 34 0 31 6 30 3 125 60 4 59 3 57 3 55 6 53 7 50 0 51 1 47 8 40 5 57 8 57 0 54 5 51 9 49 2 48 0 44 7 44 1 40 4 250 64 0 62 3 61 0 59 9 58 5 55 1 51 2 45 9 34 9...

Page 7: ...6 55 0 57 7 54 5 48 5 47 3 48 4 39 8 38 9 125 64 5 61 9 60 4 58 5 56 9 54 6 52 4 46 1 39 1 60 1 58 3 56 8 53 7 50 9 48 3 48 0 41 6 33 9 250 71 9 72 0 69 5 68 0 60 3 56 6 50 9 46 0 38 3 59 1 58 2 56 9...

Page 8: ...N 3 BU 4 950764 950511 950511 950764 13 951158 7025700 951154 951150 950764 1 2 9 8 L M 3 4 5 6 9 5 0 6 8 6 10 11 12 S 2 S 1 950764 950764 10VDC 946070 T1 1 4 2 B SC S 10VDC N S 2 G Y 1 B U 4 BN 3 GN...

Page 9: ...nnecting a pipe to the water seal the water condensing from extract air can be led to a floor drain not directly to the drain The pipe must not rise after the water seal For further instructions on th...

Page 10: ...plate 3335110 7 Fan fastening angle 1088410 8 Fan housing metal parts inlet cone partition and insulation 50 MC SC BP 3463100 3463200 3463300 8 Fan housing metal parts inlet cone partition and insula...

Page 11: ...3488700 26 G4 filter stand 500 mm supply air 50 MC SC BP 3356400 26 G4 filter stand 580 mm supply air 80 MC SC BP 3352700 27 G4 filter stand 400 mm extract air 50 MC SC BP 3382800 27 G4 filter stand...

Page 12: ...12 SC BP Vallox TSK Multi 50 80 VALLOX We reserve the right to make changes without prior notice What the units include can vary depending on the sales area 1 09 609E 22 4 2014 PDF www vallox com...