background image

8

© VALLOX • We reserve the right to make changes without prior notice.

What the units include can vary depending on the sales area.

Vallox

121

SE

Symptom

Cause

Do this

1

Outdoor air coming to the 

dwelling is cold.

• Air cools down in the attic ducts.
• The heat recovery cell is frozen, which is why extract air 

cannot heat outdoor air.

• The post-heating radiator does not work. 
• The extract air filter or cell is clogged. 
• The initial adjustment of ventilation has not been done.

• Check the insulation of the attic ducts.
• Check the cleanliness of the filters and heat recovery cell. 

2

The maintenance reminder 

symbol (

 

) is displayed 

and the unit operates 

otherwise normally.

• The maintenance reminder lights up the maintenance 

reminder symbol in the main display of the control panel at 

an interval of circa 4 months (factory setting). 

• You may change the interval (see the operating instructions 

for control panel, Section 3.2).

•  Check the cleanliness of the filters and the unit. If needed, clean or 

replace the filters. Also check the external grille.

•  Reset the maintenance reminder symbol (see the operating 

instructions for control panel, Section 3.1.).

3

“Exh air sensor faulty” 

message is displayed and 

the unit is stopped.

• There is a fault in the freezing protection sensor.

•  Contact a maintenance company. Sensor mounting needs to be 

checked and the sensor has to be replaced if necessary.

4

“Sup. air sensor faulty” 

message is displayed and 

the unit is stopped.

• There is a fault in the supply air sensor.

•  Contact a maintenance company. Sensor mounting needs to be 

checked and the sensor has to be replaced if necessary.

5

“Ind. air sensor faulty” 

message is displayed and 

the unit is stopped.

• There is a fault in the extract air sensor.

•  Contact a maintenance company. Sensor mounting needs to be 

checked and the sensor has to be replaced if necessary.

6

“Out. air sensor faulty” 

message is displayed and 

the unit is stopped.

• There is a fault in the outdoor air sensor.

•  Contact a maintenance company. Sensor mounting needs to be 

checked and the sensor has to be replaced if necessary.

7

“Cell sensor faulty” 

message is displayed and 

the unit is stopped.

• There is a fault in the sensor of the heat recovery cell.

•  Contact a maintenance company. Sensor mounting needs to be 

checked and corrected if necessary.

8

"Bus fault" message is 

displayed and the unit 

operates at speed 1 (check 

the fan speed).

•  Wiring fault in the carbon dioxide sensor, in the control 

panel or in the humidity sensor, or the cable is of the wrong 

type.

•  Contact a maintenance company. The connections have to be 

checked and corrected if necessary.

9

“Freezing alert” message 

is displayed and the unit is 

stopped.

•  Antifreeze of the water-circulating radiator is active.
    NOTE! If there is no non-freezing solution in the water of 

the radiator, the radiator is at risk of freezing.   

(Does not apply to the Vallox 121 SE unit)

•  Immediately troubleshoot the situation. Consult a maintenance 

company to find out if there is any non-freezing solution in the 

radiator. Check if the circulation pump is broken, the boiler out of 

operation etc. The situation may pass by itself as soon as supply air 

temperature exceeds 10 degrees, but do not wait till it happens.

10

The desired automatic 

adjustment does not stay 

on.

•  There is a fault in the humidity or carbon dioxide sensor. 

One of the sensors is broken or missing.

•  Contact a maintenance company. Sensor mounting and connections 

have to be checked. (Sensors are options.)

11

The fans are not running 

and no indicator light is lit 

at the control panel.

•  Door switch may be broken or the door is not quite closed.
•  The unit is out of power, for instance because a fuse has 

blown.

•  The glass tube fuse (located in the control card behind a 

protecting plate) protecting the electronics inside the unit 

may have blown.

•  Check the door switch and fuses. The unit has a T800 mA glass-tube 

fuse.

•  If needed, contact a maintenance company (for instance to check 

the glass tube fuse).

12

The unit does not obey the 

control panel.

•  Disconnect the plug of the unit from the wall socket, wait for 30 

seconds and put the plug back. If this does not help, contact a 

maintenance company.

13

“Carbon dioxide alarm” 

message is displayed and 

the unit is stopped.

•  Carbon dioxide alarm. Carbon dioxide content has 

exceeded 5000 PPM for two minutes. May be caused by 

for instance a fire.

•  If there is a fire, take the necessary steps.
•  You can make the unit operational by disconnecting the plug from 

the wall socket, waiting for 30 seconds and putting the plug back.

14

Filter guard symbol  

( ) is displayed and the 

unit operates 

otherwise normally.

•  The pressure in the filter guard (pressure difference switch) 

has risen above the adjustment value or speed is 7 or 8 

(option).

•  Check the cleanliness of the filters and the unit. If needed, clean or 

replace the filters. Also check the external grille.

Troubleshooting

MAINTENANCE INSTRUCTIONS

Summary of Contents for VALLOX 121 SE Series

Page 1: ...de A3560 Models VALLOX 121 SE R VALLOX 121 SE L Electrical connection 230 V 50 Hz 5 7 A Degree of protection provided by enclosures IP 34 Fans direct current Extract air 0 117 kW 0 9 A 106 dm3 s 100 Pa DC Supply air 0 117 kW 0 9 A 104 dm3 s 100 Pa Heat recovery Cross counter flow cell η 80 Heat recovery bypass Automatic Electric post heating unit standard 900 W 3 9 A Fans Supply air G4 and F7 Extr...

Page 2: ...ding to the highest measuring result 1 5 carbon dioxide sensors can be connected as options to the VALLOX 121 SE unit The adjustment is switched on off and if needed the setpoint 500 2000 ppm is set at the control panel The factory set ting is 900 ppm The recommended maximum carbon dioxide content in good indoor air is circa 1 000 ppm During control the control panel can be used to raise fan speed...

Page 3: ...amples of such situations are high humidity loads such as a swimming pool or a situation where the exhaust air duct has frozen through Remember Switch post heating off when it starts to get too warm in the dwelling because of warm weather Switch post heating on again when it gets cooler in autumn Post heating indicator light Maintenance reminder symbol Maintenance reminder The maintenance reminder...

Page 4: ...nu To settings menu see manual In order to move to the Settings menu press the and buttons simultaneous ly In the Settings menu you can chan ge setpoints for the ventilation unit 2 3 Week clock control Week program on Week clock control can be switched on with the button and off with the button Week clock control is on when the week clock control symbol is in the main display In week clock control...

Page 5: ...ctory settings can be restored by pressing the and buttons simultaneously Remember to ensure that the setpoints are in accordance with the factory settings for this unit 3 16 Choosing cascade adjustment for supply air temperature Cascade adjust off Cascade adjustment is chosen to be on or off with the and buttons 3 17 Choosing post heating for the unit Radiator type Electric rad A water or electri...

Page 6: ...fan speed 2 Sp 2 supply air temperature 17 C Temp 17 Move the cursor to the following hour Monday D 1 16 00 H 16 fan speed 4 Sp 4 supply air temperature 20 C Temp 20 Move the cursor to the following hour Monday D 1 19 00 H 19 fan speed 6 Sp 6 supply air temperature no change Temp N Move the cursor to the following hour Monday D 1 21 00 H 21 fan speed 4 Sp 4 supply air temperature no change Temp N ...

Page 7: ... by pulling carefully Place a thin sheet board or paper under the fan in order to prevent the bottom tank from being scratched when removing the fan Unfasten the fixing screw of the fan H hex socket head cap screw AV 4 mm and place the fan on the bottom tank Rotate the fan R model anticlockwise L model clockwise and slide the fan along the bottom tank Unfasten the quick couplings of the fan wires ...

Page 8: ...tes at speed 1 check the fan speed Wiring fault in the carbon dioxide sensor in the control panel or in the humidity sensor or the cable is of the wrong type Contact a maintenance company The connections have to be checked and corrected if necessary 9 Freezing alert message is displayed and the unit is stopped Antifreeze of the water circulating radiator is active NOTE If there is no non freezing ...

Page 9: ...ded operating range Volume flow rate Sound power level in supply air duct one duct by octave band LW dB Sound power level in extract air duct one duct by octave band LW dB ADJUSTMENT POSITION AIR FLOW dm3 s ADJUSTMENT POSITION AIR FLOW dm3 s Adjustment position 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 Air flow dm3 s 25 7 41 5 51 0 53 9 58 8 75 6 78 8 101 0 29 5 41 3 43 8 51 9 60 8 70 7 75 3 96 0 Medium fre...

Page 10: ...t R2 Post heating radiator M Damper motor 24 VAC Wire colours s blue m black r brown va white vi green p red h grey kv yellow green 16 V 0 V 0 V 230 V 7023500 2011 11 17 JK M1 GND A B PWM1 PWM2 S RH2 S RH1 L N NO NC 90 C 130 C R2 L N L r N N L L1 L2 L3 N1 L4 NC GND PWM 1 s s r r s s kv kv p p k k HK 0 10V DC A B M S S 1 2 S S RH1 RH2 12x0 25mm 3184600 PWM 2 r s s kv kv r r h h 5 10 3 1 NOL R r s T...

Page 11: ...ake sure that its address is 1 If control panels have the same address they go to bus fault state In this case remove one of the control panels and change the address of the other panel The above mentioned situation can arise in connection with the later installation of an additional control panel External electrical connection Vallox 121 SE code A3560 METAL M WHITE 2 B ORANGE 2 A WHITE 1 ORANGE 1...

Page 12: ...g water connections The delivery includes a Silent Kick water seal By connecting a pipe to the water seal the water condensing from extract air can be led to a floor drain not directly to the drain Silent Klick water seal prevents the sound caused by water as the water seal dries up The pipe must not rise after the water seal The condensation water discharge outlet is located at the rear edge in t...

Reviews: