Low-energy ventilation unit
with heat recovery
© Vallox
1.09.399B EN
Updatet
26.1.2015
Valid from:
26.1.2015
1 Supply air fan
2 Extract air fan
3 Post-heating radiator, electric,
900 W (behind supply air heater)
4 Bypass duct heater, electric,
900 W (only TSK Multi 80 MC,
behind HR cell)
5 Heat recovery cell
6 Outdoor air fi lter F7
7 Outdoor air fi lter G4
8 Extract air fi lter G4
9 Automatic summer/winter damper
10 Safety switch
11 Adjustment of relationship between
supply and extract air
12 Adjustment of supply air
temperature and
summer/winter function
13 Speed selector switch (1-4)
(option)
13
Models
TSK Multi 50 MC 3603
TSK Multi 80 MC 3602
Operating, maintenance and technical instructions
VALLOX TSK MULTI 50 MC
VALLOX TSK MULTI 80 MC
Electrical connection
230 V, 50 Hz, = 4.5 A
230 V, 50 Hz, = 8.8 A
Degree of protection
provided by enclosures
IP 34
IP 34
Integrated direct-current fan
Extract air
0.043 kW 0.32 A 57 dm
3
/s 100 Pa 0.071 kW 0.5 A 93 dm
3
/s 100 Pa
Supply air
0.043 kW 0.32 A 49 dm
3
/s 100 Pa 0.071 kW 0.5 A 76 dm
3
/s 100 Pa
Heat recovery
Cross-counter fl ow cell,
> 80%
Cross-counter fl ow cell,
> 80%
Heat recovery bypass
Automatic
Motorised damper
Electric post-heating unit
900 W, 3.9 A
max 900 W, 3.9 A
Bypass duct heater
-
900 W, 3.9 A
Filters
Supply air
G4 + F7
G4 + F7
Extract air
G4
G4
Weight
45.0 kg
58.5 kg
Ventilation power adjustment
SC controller, 0-10 VDC
SC controller, 0-10 VDC
Remote monitoring control 0-10 VDC
Remote monitoring control 0-10 VDC
Options
SC controller
SC controller
SlimLine PTXP MC cooker hood
SlimLine PTXP MC cooker hood
SlimLine PTXPA MC cooker hood
SlimLine PTXPA MC cooker hood
TECHNICAL DATA