8. GAS SUPPLY CONNECTION
A nut and olive are provided for an 8mm pipe inlet connection to the ‘T’ connector at
the bottom front of the appliance. The ‘T’ connector can be rotated to allow a
connection from any direction and includes a valve for isolating the gas supply and a
pressure test point.
The supply pipe must be rigid material. Flexible pipe must not be used.
Concealed Supply Pipe Connection
If a concealed connection from inside the fireplace is required then
,
before the
appliance is fitted into the fireplace
it will be necessary to extend the supply line so
that it will project through the hole in the back of the convection box and run to the ‘T’
connector at the front. The pipe run from the supply line up to the rear opening in the
convection box must be kept away from the area which will be taken by the
convection box when it is installed (See figure 7).
Note that the centre of the appliance inlet ‘T’ connector is 25mm above the fireplace
floor. The inlet ‘T’ connector should be fitted to the supply pipe at this stage.
9. PREPARING APPLIANCE FOR INSTALLATION
IMPORTANT
Before continuing with the installation of this gas fire the aeration setting on the
burner must be checked. The aeration is factory set and should not require
adjustment. See section 17.1 (Servicing and parts replacement).
1.
Unscrew and remove the knurled screw
connecting the slider control arm to the
burner module. Lift the slider control knob,
moving the control arm away from the
burner module.
2.
Unscrew and remove the left and right
hand window brackets (See figure 10).
©
Baxi Heating U.K. Limited 2008.
Page 20
Figure 10. Window bracket removal
INSTALLER GUIDE