If the smoke is drawn into the appliance, continue with the installation.
If the test is
not satisfactory, disconnect the appliance and advise the customer of the cause
of failure.
8.
VERY IMPORTANT: The smoke match tube must remain with the fire.
Place
the smoke match tube in the recess at the bottom left hand side of the fire. A label will
indicate where it is to be placed.
14.2 Flame supervision and spillage monitoring system.
The pilot unit incorporates a system that will automatically shut off the gas supply if
the pilot flame goes out or if there is insufficient oxygen due to spillage or lack of
ventilation.
Check that the system operates properly as follows;
Light the appliance. Set at the HIGH position and leave for one minute.
Turn back to OFF to extinguish the pilot. Note the time when the pilot goes out.
Listen for a snap sound at the gas tap. Note the time when the sound is heard. This
sound is caused by an electromagnetic valve shutting off the gas supply through the
tap. The valve is located in the body of the tap. The valve should operate within 60
seconds of the pilot going out. If the valve does not operate within this time limit do
not allow the appliance to be used until the fault has been corrected.
This
monitoring system must not be adjusted, bypassed or put out of operation.
This monitoring system, or any of its parts, must only be exchanged using
Valor Fires authorised parts.
15. FITTING THE HEAT BAFFLE
1.
The fire is supplied with a heat baffle. Locate the heat baffle to the top of the fire as
shown in figure 25.
Page 34
©
Baxi Heating U.K. Limited 2010.
INSTALLER GUIDE
Figure 25.
Summary of Contents for 964
Page 7: ...1 IMAGE Page 7 Baxi Heating U K Limited 2010 INSTALLER GUIDE Blenheim fascia ...
Page 22: ...Page 22 Baxi Heating U K Limited 2010 INSTALLER GUIDE Figure 8 Pack contents ...
Page 45: ...IMAGE Page 45 Baxi Heating U K Limited 2010 OWNER GUIDE Blenheim fascia ...
Page 57: ...Page 57 Baxi Heating U K Limited 2010 OWNER GUIDE ...