DSBA3400 • Rév. 09/06/2020
36
EN
Following a power fail-
ure, the BBPR unit will
reset after 4 minutes
BBPR : description
Actuators with integrated battery backup system (on-off wiring mandatory)
BBPR model integrate a battery pack monitored by an electronic board inside the actuator. Its function is to relay
in case of power supply failure on terminal PIN 1,2 and 3 of the actuator. The BBPR system can be set on differ-
ent position like normally open (NO) or normally closed (NC). It depends on the application.
The electronic board monitors the battery pack and check the status of battery (cycle load and failure)
If a battery failure is detected , a contact on PIN 65 and 66 switch off. It’s possible to use this contact to be
aware that there is a failure on battery in the actuator without remove cover and plan the replacement.
Fail safe option required ON/OFF mode.
REP
BORNES DESCRIPTION
C1
17 (-)
18 (+)
power supply connector
C2
F (+)
F (-)
T (+)
Battery unit connector
C3
A
B
C
Motor connector
C4
1)
D3
D4
Failure feedback connector
C5
1)
65
66
Charging feedback connector
C6
A
0
B
RS485 connector
J1 Bluetooth
®
activation jumper
1) The auxiliary cables must be connected to inside installation only
Charging electronic board
LED
DESCRIPTION
ACT
Power supply:
Slow blinking (1 s) : charged battery
Rapid blinking (0.5 s) : battery charging
ERROR
Error detected:
Timestamp memory empty/scheduler selected
Clock failure
Excessive temperature
Excessive torque
HORO Weekly scheduler functioning mode
MANU manual / Bluetooth
®
functioning mode
WIRE Electric
wiring
mode
Voltage
24 V DC
Charging status feedback relay (65/66)
24 V DC - 1 A max
Battery capacity
600 mAh
Failure feedback relay (D3/D4)
24 V DC - 3 A max
Charging current
180 mA
Température
-10 °C to +40 °C
battery charge maximum duration
3,5 h
C1
C2
C5
C6
J1
C3
C4
LED
The factory default configuration is "normally closed"