background image

  

 

 

VAL

S

TEAM

 

ADCA

                       

 

 

We reserve the right to change the design and material of this product without notice.

 

 

        IMI 1.335 E 03.14

 

 

INSTALLATION AND MAINTENANCE INSTRUCTIONS 

FLOAT & THERMOSTATIC STEAM TRAPS 

FLT17 

 

GENERAL 

 

 

These  instructions  must  be  carefully  read  before  any  work  involving  products  supplied  by  VALSTEAM  ADCA 
ENGINEERING S.A. is undertaken. 
 

 

The installation procedure is a critical stage in a life of a steam trap and care should be taken to avoid damage 
to the trap or equipment. 

 

Warning!  

-  At  start  up,  the  presence  of  small  particles  in  the  water  (dirt,  scale,  weld  splatters,  etc)  may  cause  an  imperfect 
closure of the seat. If this occurs, proceed to an accurate cleaning. 
- Do not touch the equipment without appropriate protection during working operation because it may conduct heat 
if the used fluid is at high temperature. 
- Before starting maintenance be sure that the equipment is not pressurized or hot. 
- The equipments must be used  within the  working temperature and pressure  limits laid down for them, otherwise 
they may fail (refer to nameplate and/or IS- Information Sheet). 
- Do not remove the nameplate attached to the equipment. Serial number and other useful information is stamped 
on it. 
 

INSTALLATION 

 

 

 

 
-  Before  to  install  remove  plastic  covers  placed  on  flanges  or  connection  ends.  The  equipment  has  an  arrow  or 
Inlet/Outlet designations. Be sure that it will be installed on the appropriate direction. 
- Install the steam trap in the point of the system, where the condensate tends to collect. It must be installed with the 
float lever in horizontal plane, so that it rises and falls vertically. An ADCA strainer should be installed upstream of 
the trap. 

 

 
 
 

 

 

 
 
 

 
 
 
 
 
 
 

 

 

BODY LIMITING CONDITIONS 

 

  FLANGED 

   PN16 * 

FLANGED 

ANSI 150 lb ** 

RELATED 

TEMPERATURE 

ALLOWABLE  

PRESSURE 

ALLOWABLE 

PRESSURE 

16 bar 

15,4 bar 

100 ºC 

15,5 bar 

14,6 bar 

150 ºC 

14,7 bar 

13,8 bar 

200 ºC 

13,9 bar 

12,1 bar 

250 ºC 

PMO 

– Max. operating pressure           14 bar 

TMO 

– Max. operating temperature     198 ºC 

*Acc. to EN1092-2:2007 ; **Acc. to EN1759-1:2004 
Body limiting conditions PN16 or below, depending on the 
type of connection adopted. PN16 for thread. 

FLT 17-4,5

4,5 bar

FLT 17-10

10 bar

FLT 17-14

14 bar

MAX. DIFFERENTIAL PRESSURE

Summary of Contents for FLT17

Page 1: ...limits laid down for them otherwise they may fail refer to nameplate and or IS Information Sheet Do not remove the nameplate attached to the equipment Serial number and other useful information is stamped on it INSTALLATION Before to install remove plastic covers placed on flanges or connection ends The equipment has an arrow or Inlet Outlet designations Be sure that it will be installed on the ap...

Page 2: ...y to verify that they are operating correctly and to clean the internal parts and screen if any When reassembling make sure that all gasket faces are clean and always use a new gasket Tighten cover bolts uniformly in a diagonal sequence For further information refer to the relevant FLT17 brochure or consult our Sales Office TROUBLESHOOTING If the malfunctions cannot be solved with the help of the ...

Page 3: ...Replace Install an additional air eliminator Check maximum flow rate during start up PARTS LIST FOR FLT 17 STEAM TRAPS DN 1 2 1 DN15 DN25 TRAP SIZE DN A 92 1502 015 Valve seat float gasket D P 4 5bar DN1 2 1 3 4 5 6 7 1Set A 92 1503 015 Valve seat float gasket D P 10 bar DN1 2 1 3 4 5 6 7 1Set A 92 1504 015 Valve seat float gasket D P 14 bar DN1 2 1 3 4 5 6 7 1Set A 92 1502 115 Float gasket DN1 2 ...

Page 4: ...d tightening torques FLT17HC DN 1 DN25 TRAP SIZE DN 4 1 50 5 8 1 50 5 9 1 80 5 POS NR Nm Remarks Tighten cover bolts uniformly PARTS LIST FOR FLT 17 STEAM TRAPS DN 11 2 2 DN40 50 TRAP SIZE DN A 92 1502 040 Valve seat float gasket D P 4 5bar DN11 2 2 3 4 5 6 7 1Set A 92 1503 040 Valve seat float gasket D P 10 bar DN11 2 2 3 4 5 6 7 1Set A 92 1504 040 Valve seat float gasket D P 14 bar DN11 2 2 3 4 ...

Page 5: ... or mechanical damage that may represent a health safety or environmental risk must be provided in writing by the distributors and costumers when returning products to Valsteam ADCA engineering Health and safety data sheets regarding substances identified as hazardous or potentially hazardous must be provided with the information mention above LOSS OF WARRANTY Total or partial disregard of above i...

Reviews: