IMI 1.335 E 03.14
Excessive back pressure.
Damaged float.
Replace the steam trap by a
superior DN or use ADCAMAT.
Replace.
Temporary condensate
accumulation
Steam blocking.
Downsizing.
Use a steam trap with SLR.
Check maximum flow rate (during
start-up)
Slow initial start up
Damaged air eliminator.
The air flow is too high for the trap.
Downsizing.
Replace.
Install an additional air eliminator.
Check maximum flow rate (during
start-up)
PARTS LIST FOR FLT 17 -
STEAM TRAPS DN 1/2”- 1”, DN15-DN25
TRAP SIZE
DN
A.92.1502.015 Valve, seat, float & gasket D.P.4,5bar
DN1/2”-1”
3, 4, 5, 6, 7
1Set
A.92.1503.015 Valve, seat, float & gasket D.P.10 bar
DN1/2”-1”
3, 4, 5, 6, 7
1Set
A.92.1504.015 Valve, seat, float & gasket D.P.14 bar
DN1/2”-1”
3, 4, 5, 6, 7
1Set
A.92.1502.115
Float & gasket
DN1/2”-1”
3, 7
1Set
A.92.1502.215
Air vent & gasket
DN1/2”-1”
3, 8
1Set
CODE
DESIGNATION
QTY.
POS.NR.
Recommended tightening torques FLT17
DN 1/2”-1”, DN15-DN25
TRAP SIZE
DN
4
1/2
”-1”
50±5
8
1/2
”-1”
50±5
9
1/2
”-1”
70±5
POS.NR.
Nm
Remarks: Tighten cover bolts uniformly.