We reserve the right to change the design and material of this product without notice.

 

 

        IMI 1.335 E 03.14

 

 

Excessive back pressure. 
 
 
Damaged float. 
 

Replace the steam trap by a 
superior DN or use ADCAMAT. 
 
Replace. 

 
Temporary condensate 
accumulation 
 

Steam blocking. 
 
Downsizing. 

 
Use a steam trap with SLR. 
 
Check maximum flow rate (during 
start-up) 

Slow initial start up 

 
Damaged air eliminator. 
 
The air flow is too high for the trap. 
 
Downsizing. 

 
Replace. 
 
Install an additional air eliminator. 
 
Check maximum flow rate (during 
start-up) 

 
 

PARTS LIST FOR FLT 17 - 

STEAM TRAPS DN 1/2”- 1”, DN15-DN25 

 

TRAP SIZE

DN

A.92.1502.015 Valve, seat, float & gasket D.P.4,5bar

DN1/2”-1”

3, 4, 5, 6, 7

1Set

A.92.1503.015 Valve, seat, float & gasket D.P.10 bar

DN1/2”-1”

3, 4, 5, 6, 7

1Set

A.92.1504.015 Valve, seat, float & gasket D.P.14 bar

DN1/2”-1”

3, 4, 5, 6, 7

1Set

A.92.1502.115

Float & gasket  

DN1/2”-1”

3, 7

1Set

A.92.1502.215

  Air vent & gasket  

DN1/2”-1”

3, 8

1Set

CODE

DESIGNATION

QTY.

POS.NR.

 

 
 

Recommended tightening torques FLT17 

DN 1/2”-1”, DN15-DN25 

    

TRAP SIZE

DN

4

1/2

”-1” 

50±5

8

1/2

”-1” 

50±5

9

1/2

”-1” 

70±5

POS.NR.

Nm

 

Remarks: Tighten cover bolts uniformly. 

 

 
 
 

Summary of Contents for FLT17

Page 1: ...limits laid down for them otherwise they may fail refer to nameplate and or IS Information Sheet Do not remove the nameplate attached to the equipment Serial number and other useful information is stamped on it INSTALLATION Before to install remove plastic covers placed on flanges or connection ends The equipment has an arrow or Inlet Outlet designations Be sure that it will be installed on the ap...

Page 2: ...y to verify that they are operating correctly and to clean the internal parts and screen if any When reassembling make sure that all gasket faces are clean and always use a new gasket Tighten cover bolts uniformly in a diagonal sequence For further information refer to the relevant FLT17 brochure or consult our Sales Office TROUBLESHOOTING If the malfunctions cannot be solved with the help of the ...

Page 3: ...Replace Install an additional air eliminator Check maximum flow rate during start up PARTS LIST FOR FLT 17 STEAM TRAPS DN 1 2 1 DN15 DN25 TRAP SIZE DN A 92 1502 015 Valve seat float gasket D P 4 5bar DN1 2 1 3 4 5 6 7 1Set A 92 1503 015 Valve seat float gasket D P 10 bar DN1 2 1 3 4 5 6 7 1Set A 92 1504 015 Valve seat float gasket D P 14 bar DN1 2 1 3 4 5 6 7 1Set A 92 1502 115 Float gasket DN1 2 ...

Page 4: ...d tightening torques FLT17HC DN 1 DN25 TRAP SIZE DN 4 1 50 5 8 1 50 5 9 1 80 5 POS NR Nm Remarks Tighten cover bolts uniformly PARTS LIST FOR FLT 17 STEAM TRAPS DN 11 2 2 DN40 50 TRAP SIZE DN A 92 1502 040 Valve seat float gasket D P 4 5bar DN11 2 2 3 4 5 6 7 1Set A 92 1503 040 Valve seat float gasket D P 10 bar DN11 2 2 3 4 5 6 7 1Set A 92 1504 040 Valve seat float gasket D P 14 bar DN11 2 2 3 4 ...

Page 5: ... or mechanical damage that may represent a health safety or environmental risk must be provided in writing by the distributors and costumers when returning products to Valsteam ADCA engineering Health and safety data sheets regarding substances identified as hazardous or potentially hazardous must be provided with the information mention above LOSS OF WARRANTY Total or partial disregard of above i...