VAMP 210
Generator protection relay
Operation and configuration
VAMP Ltd
20
Vamp 24h support phone: +358 (0)20 753 3264
VM210.EN004
4.2.
Operation indicators
LED indicator
Meaning
Measure/ Remarks
Power LED lit
The auxiliary power has
been switched on
Normal operation state
Error LED lit
An internal relay fault has
been detected
The relay attempts to
reboot. [REBOOT]. If the
error LED remains lit,
call for maintenance.
Com LED lit or
flashing
The serial bus is in use
and transferring
information
Normal operation state
Alarm LED lit
One or several signals of
the output relay matrix
have been assigned to
output Alarm and the
output has been activated
by one of the signals.
(Output relay
configuration, see chapter
5.4 on page 25)
The LED is switched off,
when the signal that
caused output Alarm to
activate, e.g. the START
signal, is reset. The
resetting depends on the
type of configuration,
Connected or Latched.
Trip LED lit
One or several signals of
the output relay matrix
have been assigned to
output Trip and the output
has been activated by one
of the signals. (Output
relay configuration, see
chapter 5.4 on page 25)
The LED is switched off,
when the signal that
caused output Trip to
activate, e.g. the TRIP
signal, is reset. The
resetting depends on the
type of configuration,
Connected or Latched.
A- C LED lit
Application- related status
indications
Resetting latched indicators and output relays
All indicators and output relays can be given a latching
function in the configuration.
There are two ways to reset latched indicators and relays:
1.
Move to the initial display, see Figure 2.2.1-1, from the
alarm list, by pushing the CANCEL key for approx. 3 s.
Then reset the latched indicators and output relays by
pushing the ENTER key.
2.
Acknowledge each event in the alarm list one by one, by
pushing ENTER the equivalent times. Then, in the initial
display, reset the latched indicators and output relays by
pushing the ENTER key.
The latchings can also be reset via the communications bus or
via a DI input configured for that purpose.