VAMP 210
Generator protection relay
Technical description
VAMP Ltd
20
Vamp 24h support phone: +358 (0)20 753 3264
VM210.EN004
Connecting two cable CTs on both sides of the generator in
series a differential earth fault protection can be used. This
offers a good selectivity in case the cable capacitance between
the two CTs is small.
The other two earth fault current stages use the input I
02
.
Using an external injection device like VEO-MSV these stages
can be used for rotor earth fault detection.
Figure 2.2.5-1 Block diagram of the earth fault stage I
0
>.
Figure 2.2.5-2 Block diagram of the earth fault stage I
0
>>.